DEHU
Dehumidification Config 0 to 3 DHSELECT 0
Dehumidification Sensor 1 to 3 DHSENSOR 1
Econ disable in DH mode? Yes/No DHECONEN No
Vent Reheat Setpt Select 0 to 1 DHVHTCFG 0
Vent Reheat RAT offset 0 to 8 ^F DHVRAOFF 0
Vent Reheat Setpoint 55 to 95 dF DHVHT_SP 70
Dehumidify Cool Setpoint 40 to 55 dF DHCOOLSP 45
Dehumidify RH Setpoint 10 to 90 % DHRELHSP 55
Humidimizer Adjust Rate secs HMZRRATE
Humidimizer Prop. Gain HMZR_PG
Bypass EXV Max Open % BYP_MAX
Condenser EXV Max Open % COND_MAX
LAT Sample Buffer Length LAT_SAMP
LAT Sample Rate seconds secs LAT_RATE
DISP
Metric Display Off/On DISPUNIT Off
Language Selection 0 to 1 LANGUAGE 0
Password Enable Enable/Disable PASS_EBL Enable
Service Password 0000 to 9999 PASSWORD 1111
Contrast Adjustment 0 to 255 CNTR_ADJ 0
Brightness Adjustment 0 to 255 BRTS_ADJ 0
DLVT
Dmd Level Lo Heat On –1 to 2 ^F DMDLHON 1.5
Dmd Level(+) Hi Heat On 0.5 to 20.0 ^F DMDHHON 0.5
Dmd Level(-) Lo Heat Off 0.5 to 2.0 ^F DMDLHOFF 1
Dmd Level Lo Cool On –1 to 2 ^F DMDLCON 1.5
Dmd Level(+) Hi Cool On 0.5 to 20.0 ^F DMDHCON 0.5
Dmd Level(-) Lo Cool Off 0.5 to 2.0 ^F DMDLCOFF 1
Cool Trend Demand Level 0.1 to 5.0 ^F CTRENDLV 0.1
Heat Trend Demand Level 0.1 to 5.0 ^F HTRENDLV 0.1
Cool Trend Time 30 to 600 sec CTRENDTM 120
Heat Trend Time 30 to 600 sec HTRENDTM 120
DMDL
Demand Limit Select 0 to 3 DMD_CTRL 0
Demand Limit at 20 ma 0 to 100 % DMT20MA 100
Loadshed Group Number 0 to 99 SHED_NUM 0
Loadshed Demand Delta 0 to 60 % SHED_DEL 0
Maximum Loadshed Time 0 to 120 min SHED_TIM 60
Demand Limit Sw.1 Setpt. 0 to 100 % DLSWSP1 80
Demand Limit Sw.2 Setpt. 0 to 100 % DLSWSP2 50
ECON
Economizer Installed? Yes/No ECON_ENA Yes
Econ. Act.2 Installed? Yes/No ECON_TWO No
Economizer Min.Position 0 to 100 % ECONOMIN 5
Economizer Max.Position 0 to 100 % ECONOMAX 98
Economzr trim for sumZ? Yes/No ECONTRIM Yes
Econ ChangeOver Select 0 to 3 ECON_SEL 0
OA Enthalpy ChgOvr Selct 1 to 5 OAEC_SEL 4
Outdr.Enth Compare Value 18 to 28 BTU/LBM OAEN_CFG 24
High OAT Lockout Temp 55 to 120 dF OAT_LOCK 60
OA Dewpoint Temp Limit 50 to 62 dF OADEWCFG 55
Outside Air RH Sensor Enable/Disable OARHSENS Disable
Outdoor Air CFM Sensor Enable/Disable OCFMSENS Disable
Economizer Min.Flow 0 to 20000 CFM OACFMMAX 2000
IAQ Demand Vent Min.Flow 0 to 20000 CFM OACFMMIN 0
Econ.Min.Flow Deadband 200 to 1000 CFM OACFM_DB 400
Economizer Prop.Gain 0.7 to 3.0 EC_PGAIN 1
Economizer Range Adjust 0.5 to 5 ^F EC_RANGE 2.5
Economizer Speed Adjust 0.1 to 10 EC_SPEED 0.75
Economizer Deadband 0.1 to 2 ^F EC_DBAND 0.5
Unoc Econ Free Cool Cfg 0 to 2 UEFC_CFG 0
Unoc Econ Free Cool Time 0 to 720 min UEFCTIME 120
Un.Ec.Free Cool OAT Lock 40 to 70 dF UEFCNTLO 50
Econ Serial Number 1 0 to 9999 ECON_SN1
Econ Serial Number 2 0 to 6 ECON_SN2
Econ Serial Number 3 0 to 9999 ECON_SN3
Econ Serial Number 4 0 to 254 ECON_SN4
Econ Ctrl Angle Lo Limit 0 to 90 ECONCALM 85
Econ 2 Serial Number 1 0 to 9999 ECN2_SN1
Econ 2 Serial Number 2 0 to 6 ECN2_SN2
Econ 2 Serial Number 3 0 to 9999 ECN2_SN3
Econ 2 Serial Number 4 0 to 254 ECN2_SN4
Ecn2 Ctrl Angle Lo Limit 0 to 90 ECN2CALM 85
ECON POS AT MIN VFD SPEED 0 to 100 % EPOSMNFS 5
ECON POS AT MAX VFD SPEED 0 to 100 % EPOSMXFS 5