208
IAQ_ (cont) DAQ PPM Fan On Setpoint 0 to 2000 DAQFNON 400
Diff. AQ Responsiveness –5 to 5 IAQREACT 0
OAQ Lockout Value 0 to 2000 OAQLOCK 0
User determined OAQ 0 to 5000 OAQ_USER 400
IAQ Low Reference 0 to 5000 IAQREFL 0
IAQ High Reference 0 to 5000 IAQREFH 2000
OAQ Low Reference 0 to 5000 OAQREFL 0
OAQ High Reference 0 to 5000 OAQREFH 2000
IAQ Purge Yes/No IAQPURGE No
IAQ Purge Duration 5 to 60 min IAQPTIME 15
IAQ Purge LoTemp Min Pos 0 to 100 % IAQPLTMP 10
IAQ Purge HiTemp Min Pos 0 to 100 % IAQPHTMP 35
IAQ Purge OAT Lockout 35 to 70 dF IAQPNTLO 50
ECON POS AT MIN VFD SPEED 0 to 100 % EPOSMNFS 5
ECON POS AT MAX VFD SPEED 0 to 100 % EPOSMXFS 5
OV_CFG
OV-A Nominal Motor Volts 0 to 999 volts OVA_NVLT
OV-A Nominal Motor Amps 0 to 999 amps OVA_NAMP
OV-A Nominal Motor Freq 10 to 500 OVA_NFRQ
OV-A Nominal Motor rpm 50 to 30000 OVA_Nrpm
OV-A Nominal Motor HPwr 0 to 500 OVA_NPWR
OV-A Motor Direction 0=F, 1=R OVA_MDIR
OV-A Acceleration Time 0 to 1800 secs OVA_ACCL
OV-A Deceleration Time 0 to 1800 secs OVA_DECL
OV-A Switching Frequency 0 to 3 OVA_SWFQ
OV-B Nominal Motor Volts 0 to 999 volts OVB_NVLT
OV-B Nominal Motor Amps 0 to 999 amps OVB_NAMP
OV-B Nominal Motor Freq 10 to 500 OVB_NFRQ
OV-B Nominal Motor rpm 50 to 30000 OVB_Nrpm
OV-B Nominal Motor HPwr 0 to 500 OVB_NPWR
OV-B Motor Direction 0=F, 1=R OVB_MDIR
OV-B Acceleration Time 0 to 1800 secs OVB_ACCL
OV-B Deceleration Time 0 to 1800 secs OVB_DECL
OV-B Switching Frequency 0 to 3 OVB_SWFQ
SP__
Static Pressure Control Enable/Disable STATICFG Disable
Staged Air Volume Control Enable/Disable STGAVCFG Disable
Static Pressure Sensor Enable/Disable SPSENS Disable
Static Press. Low Range –10 to 0 SP_LOW 0
Static Press. High Range 0 to 10 SP_HIGH 5
Static Pressure Setpoint 0 to 5 "H2O SPSP 1.5
VFD Minimum Speed 0 to 100 % STATPMIN 10
VFD Maximum Speed 0 to 100 % STATPMAX 100
VFD MinSpeed in HeatMode 75% 0 to 100 % HTSPMIN
VFD MaxSpeed in HeatMode 100% 0 to 100 % HTSPMAX
VFD Fire Speed Over. 0 to 100 % STATPFSO 100
Stat. Pres. Reset Config 0 to 4 (multi-text strings) SPRSTCFG 0
SP Reset Ratio 0.00 to 2.00 SPRRATIO 0.20
SP Reset Limit 0.00 to 2.00 SPRLIMIT 0.75
SP Reset Econo. Position 0 to 100 % ECONOSPR 5
Stat.Pres.PID Run Rate 5 to 120 sec SPIDRATE 15
Static Press. Prop. Gain 0 to 5 STATP_PG 0.5
Static Press. Intg. Gain 0 to 2 STATP_IG 0.5
Static Press. Derv. Gain 0 to 5 STATP_DG 0.3
SWLG
Filter Status Inpt-Clean Open/Close FLTSLOGC Open
IGC Feedback - Off Open/Close GASFANLG Open
RemSw Off-Unoc-Strt-NoOv Open/Close RMTINLOG Open
Enthalpy Input - Low Open/Close ENTHLOGC Close
Fan Status Sw. - Off Open/Close SFSLOGIC Open
Dmd.Lmt.Sw.1 - Off Open/Close DMD_SW1L Open
Dmd.Lmt.Sw.2 - Off Open/Close DMD_SW2L Open
IAQ Disc.Input - Low Open/Close IAQINLOG Open
Fire Shutdown - Off Open/Close FSDLOGIC Open
Press. Switch - Off Open/Close PRESLOGC Open
Evacuation Sw. - Off Open/Close EVACLOGC Open
Smoke Purge Sw. - Off Open/Close PURGLOGC Open
Dehumidify Sw. - Off Open/Close DHDISCLG Open
APPENDIX B — CCN TABLES (CONT)
Table O — SERVICE-CONFIG TABLES (cont)
TABLE DISPLAY NAME RANGE UNITS POINT NAME DEFAULT