209
T24_CFG
Economizer Installed? Yes/No ECON_ENA Yes
Econ.Act.2 Installed? Yes/No ECON_TWO No
SAT Settling Time secs SAT_SET 240
MBB Sensor Heat Relocate Yes/No HTLATMON No
Log Title 24 Faults Yes/No T24LOGFL No
T24 Econ Move Detect % T24ECMDB 1
T24 Econ Move SAT Test % T24ECSTS 10
T24 Econ Move SAT Change deltaF T24SATMD 0.2
T24 Econ RAT-OAT Diff deltaF T24RATDF 15
T24 Heat/Cool End Delay mins T24CHDLY 25
T24 Test Minimum Pos. % T24TSTMN 15
T24 Test Maximum Pos. % T24TSTMX 85
Economizer Deadband Temp dF AC_EC_DB 5
Econ Fault Detect Gap % EC_FLGAP 5
Econ Fault Detect Timer secs EC_FLTMR 20
Excess Air CFM CFM EX_ARCFM 150
Excess Air Detect Timer secs EX_ARTMR 800
T24 Econ Auto-Test Day T24_ECDY 0
T24 Econ Auto-Test Time T24_ECTM 2
T24 AutoTest SF Run Time mins T24ACMRT 2
T24 Auto-Test VFD Speed % T24ACSPD 20
T24 Auto-Test Econ % Opn % T24ACOPN 50
T24 Auto-Test VFD % Chng % T24VFDPC 10
TRIM
Air Temp Lvg SF Trim –10 to 10 ^F SAT_TRIM 0
RAT Trim –10 to 10 ^F RAT_TRIM 0
OAT Trim –10 to 10 ^F OAT_TRIM 0
SPT Trim –10 to 10 ^F SPT_TRIM 0
Limit Switch Trim –10 to 10 ^F LSW_TRIM 0
Air Temp Lvg Evap Trim –10 to 10 ^F CCT_TRIM 0
A1 Discharge Temp Trim –10 to 10 ^F DTA1TRIM
Suction Gas Temp A Trim –10 to 10 ^F RGTATRIM
Suct.Press.Circ.A Trim –50 to 50 SPA_TRIM 0
Suct.Press.Circ.B Trim –50 to 50 SPB_TRIM 0
Dis.Press.Circ.A Trim –50 to 50 DPA_TRIM 0
Dis.Press.Circ.B Trim –50 to 50 DPB_TRIM 0
Static Press. Trim (ma) –2 to 2 SPMATRIM 0
Bldg. Pressure Trim (ma) –2 to 2 BPMATRIM 0
Outside Air CFM Trim (ma) –2 to 2 OAMATRIM 0
Supply Air CFM Trim (ma) –2 to 2 SAMATRIM 0
Return Air CFM (ma) –2 to 2 RAMATRIM 0
UNIT
Machine Control Type 1 to 6 CTRLTYPE 4
Unit Size (30 to 100) 30 to 100 UNITSIZE 30
Fan Mode (0=auto, 1=cont) 0 to 1 FAN_MODE 1
Remote Switch Config 0 to 3 RMTINCFG 0
CEM Module Installed Yes/No CEM_BRD No
Temp.Cmp.Strt.Cool Factr 0 to 60 min TCSTCOOL 0
Temp.Cmp.Strt.Heat Factr 0 to 60 min TCSTHEAT 0
Fan fail shuts down unit Yes/No SFS_SHUT No
Fan Stat Monitoring Type 0 to 2 SFS_MON 0
VAV Unocc.Fan Retry time 0 to 720 min SAMPMINS 50
50 Hertz Unit? Yes/No UNIT_HZ No
MAT Calc Config Type 0 to 2 MAT_SEL 1
Reset MAT Table Entries? Yes/No MATRESET No
MAT Outside Air Default 0 to 100 % MATOAPOS 20
Altitude……..in feet: 0 to 60000 ALTITUDE 0
MAT Outside Air Default % MATOAPOS
Startup Delay Time 0 to 900 secs DELAY 0
Auxiliary Relay Config 0 to 3 (multi-text strings) AUXRELAY 0
Space Temp Sensor Enable/Disable SPTSENS Disable
Space Temp Offset Sensor Enable/Disable SPTOSENS Disable
Space Temp Offset Range 1 to 10 SPTO_RNG 5
Space Air RH Sensor Enable/Disable SPRHSENS Disable
Return Air RH Sensor Enable/Disable RARHSENS Disable
Filter Stat.Sw.Enabled? Enable/Disable FLTS_ENA Disable
Disable T183 Alert 0 to 1 T183DSIA
SAV Optimized for Dehumidification Yes/No SAVDEHUM
APPENDIX B — CCN TABLES (CONT)
Table O — SERVICE-CONFIG TABLES (cont)
TABLE DISPLAY NAME RANGE UNITS POINT NAME DEFAULT