EasyManua.ls Logo

Carrier Weathermaster 48P030-100 - Page 215

Carrier Weathermaster 48P030-100
306 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
215
MILLIAMP
IAQ milliamps ma IAQ_MA
OAQ milliamps ma OAQ_MA
SP Reset milliamps ma SPRST_MA
4-20 ma Demand Signal ma DMDLMTMA forcible
EDT Reset milliamps ma EDTRESMA
OARH milliamps ma OARH_MA
SPRH milliamps ma SPRH_MA
RARH milliamps ma RARH_MA
SACFM milliamps ma SACFM_MA
RACFM milliamps ma RACFM_MA
OACFM milliamps ma OACFM_MA
BP milliamps ma BP_MA
SP milliamps ma SP_MA
MODES
System Mode…………: ascii text strings
HVAC Mode…………..: ascii text strings
Control Mode………..: ascii text strings
Currently Occupied On/Off MODEOCCP
Timed Override in effect On/Off MODETOVR
DCV resetting min pos On/Off MODEADCV
Supply Air Reset On/Off MODESARS
Demand Limit in Effect On/Off MODEDMLT
Temp.Compensated Start On/Off MODETCST
IAQ pre-occ purge active On/Off MODEIQPG
Linkage Active - DAV On/Off MODELINK
Mech.Cooling Locked Out On/Off MODELOCK
HVAC Mode Numerical Form number MODEHVAC
OCCDEFME
Current Day, Time and Date: ascii date and time TIMEDATE
Occupancy Controlled By: ascii text OCDFTXT1
ascii text OCDFTXT2
ascii text OCDFTXT3
Currently Occupied Yes/No MODE_OCC
Current Occupied Time STRTTIME
Current Unoccupied Time ENDTIME
Next Occupied Day and Time NXTOC_DT
Next Unocc. Day and Time NXTUN_DT
Last Unocc. Day and Time PRVUN_DT
Current Occup. Period # PER_NO
Timed-Override in Effect Yes/No OVERLAST
Timed-Override Duration hours OVR_HRS
PRESBLDG
Building Pressure "H2O BP
Network Building Pressure –2 to 2 "H2O BP.NTWRK
Return Air CFM CFM RACFM
Supply Air CFM CFM SACFM
Power Exhaust Relay 1 On/Off PE1
Power Exhaust Relay 2 On/Off PE2
BP 1 Actuator Curr.Pos. % BP1_RPOS
BP 1 Command Position % BP1_CPOS
BP 2 Actuator Curr.Pos. % BP2_RPOS
BP 2 Command Position % BP2_CPOS
Exhaust Fan VFD Speed % EFAN_VFD
Building Pressure Setp. "H2O BPSP config
BP Setpoint Offset ^"H2O BPSO config
BP Fail Strk Count Peak BP_FSCP
BP Fail Strk Count Total BP_FSCT
Prognostics BP Enable Disable/Enable PG_BP_EN
Prognostics BP Deadband "H2O PG_BP_DB
Fan Track Learn Enable Yes/No DCFM_CFG config
Fan Track Learn Rate min DCFMRATE config
Fan Track Initial DCFM CFM DCFMSTRT config
Fan Track Max Clamp CFM DCFM_MAX config
Fan Track Max Correction CFM DCFM_ADJ config
Fan Track Internl EEPROM CFM DCFM_OFF config
Fan Track Reset Internal DCFMRSET config
Fan Track Internal RAM CFM DCFM_RAM
Fan Track Control D.CFM CFM DELTACFM
PRESDUCT
Static Pressure "H2O SP
Supply Fan Commanded % % SFAN_VFD
Economzr 2 Act.Curr.Pos. % ECN2RPOS
Econ Command Position % ECN2CPOS
Static Pressure Setpoint "H2O SPSP config
Static Pressure Reset SPRESET forcible
APPENDIX B — CCN TABLES (CONT)
Table P — MAINTENANCE DISPLAY TABLES (cont)
TABLE DISPLAY NAME RANGE UNITS POINT NAME WRITE STATUS

Table of Contents

Related product manuals