Maximum Damper Position R/W % 0 to 100 AV:3052 max_dmpr_pos_1
Maximum Reset R/W inH2O AV:3054 max_reset_1
Minimum Damper Position R/W % 0 to 100 AV:3053 min_dmpr_pos_1
Mixed Air Temperature R °F AV:1500 ma_temp_1
OAQ - PPM Outdoor CO2 R/W no unit 0 to 5000 AV:113 oaq_1
Occupied Cool Mode End R °F AV:114 occl_end_1
Occupied Cool Mode Start R °F AV:115 occlstrt_1
Occupied Heat Mode End R °F AV:116 ocht_end_1
Occupied Heat Mode Start R °F AV:117 ochtstrt_1
Occupied? R/W 0 = NO; 1 = YES BV:2008 occ_status_1
Outside Air CFM R cfm AV:66 oacfm_1
Outside Air Relative Humidity R/W % 0 to 100 AV:119 oarh_1
Outside Air Temperature R/W °F –40 to 240 AV:1003 oat_1
Power Exhaust Relay 1 R 0 = OFF; 1 = ON BV:49 pe1_1
Power Exhaust Relay 2 R 0 = OFF; 1 = ON BV:51 pe2_1
Relay 3 W1 Gas Valve 2 R 0 = OFF; 1 = ON BV:76 hs3_1
Relay 4 W2 Gas Valve 2 R 0 = OFF; 1 = ON BV:77 hs4_1
Relay 5 W1 Gas Valve 3 R 0 = OFF; 1 = ON BV:78 hs5_1
Relay 6 W2 Gas Valve 3 R 0 = OFF; 1 = ON BV:79 hs6_1
Requested Heat Stage R no unit AV:2003 heat_run_1
Return Air CFM R cfm AV:69 racfm_1
Return Air Relative Humidity R/W % 0 to 100 AV:134 rarh_1
Return Air Temperature R/W °F –40 to 240 AV:135 rat_1
Setpoint Adjustment Enable R/W
0 = DISABLE
1 = ENABLE
BV:6 stpt_adj_enable_1
SP High Alert Limit R/W H2O 0 to 5 AV:73 sph_1
SP Low Alert Limit R/W H2O 0 to 5 AV:74 spl_1
Space Relative Humidity R % AV:2606 link_rh_1
Space Relative Humidity R/W % 0 to 100 AV:72 sprh_1
Space Temp Offset Range R/W °^F 1 to 10 AV:139 spto_rng_1
Space Temperature R/W °F –40 to 240 AV:137 spt_1
Staged Gas LAT 1 R °F AV:150 lat1sgas_1
Staged Gas LAT 2 R °F AV:151 lat2sgas_1
Staged Gas LAT 3 R °F AV:152 lat3sgas_1
Static Pressure R H2O AV:1016 static_press_1
Static Pressure Reset R/W no unit 0 to 15 AV:157 spreset_1
Static Pressure Reset Enable R/W
0 = DISABLE
1 = ENABLE
BV:3051 st_pr_rst_en_1
Static Pressure Setpoint R/W H2O 0 to 5 AV:3050 sa_static_stpt_1
Supply Air CFM R cfm AV:78 sacfm_1
Supply Air Reset R 0 = OFF; 1 = ON BV:93 modesars_1
Supply Air Setpnt. Reset R/W °^F 0 to 20 AV:158 sasprset_1
Supply Air Setpoint R/W °F 45 to 75 AV:3007 sa_temp_stpt_1
Supply Fan Relay R 0 = OFF; 1 = ON BV:2001 sfan_1
Supply Fan Status Switch R/W 0 = OFF; 1 = ON BV:95 sfs_1
Supply Fan VFD Speed R % AV:2050 sf_vfd_output_1
System Cooling Demand Level R no unit AV:9006 cool_demand_level_1
System Demand Limiting R
0 = Inactive
1 = Active
BV:7 dem_lmt_act_1
System Heating Demand Level R no unit AV:9036 heat_demand_level_1
System OAT Master R °F AV:80001 mstr_oa_temp_1
System Space AQ R ppm AV:1903 system_aq_1
System Space RH R %rh AV:1904 system_rh_1
System Space Temperature R °F AV:1902 system_spt_1
Thermostat G Input R/W 0 = OFF; 1 = ON BV:1021 g_input_1
Thermostat W1 Input R/W 0 = OFF; 1 = ON BV:1019 w1_input_1
Thermostat W2 Input R/W 0 = OFF; 1 = ON BV:1020 w2_input_1
Thermostat Y1 Input R/W 0 = OFF; 1 = ON BV:1017 y1_input_1
Thermostat Y2 Input R/W 0 = OFF; 1 = ON BV:1018 y2_input_1
Unoccupied Cool Mode End R °F AV:168 uccl_end_1
Unoccupied Cool Mode Start R °F AV:169 ucclstrt_1
Unoccupied Heat Mode End R °F AV:170 ucht_end_1
Unoccupied Heat Mode Start R °F AV:171 uchtstrt_1
Use Linkage R/W 0 = NO; 1 = YES BV:2605 use_linkage_1
User Defined Analog 1 R/W no unit AV:2901 user_analog_1_1
User Defined Analog 10 R/W no unit AV:2909 user_analog_10_1
User Defined Analog 11 R/W no unit AV:2910 user_analog_11_1
APPENDIX G — UPC OPEN CONTROLLER (CONT)
NETWORK POINTS LIST (CONT)
POINT DESCRIPTION
CCN POINT
NAME
READ/
WRITE
UNITS
DEFAULT
VALUE
RANGE
BACNET
OBJECT ID
BACNET OBJECT
NAME