CL-7
CONTROLS SET POINT AND CONFIGURATION LOG (cont)
ITEM EXPANSION RANGE DEFAULT SETTING
COOL (cont) COOLING CONFIGURATION
DS.AP Dig Scroll Adjust Delta 0 to 100% 100
DS.AD Dig Scroll Adjust Delay 15 to 60 sec 20
DS.RP Dig Scroll Reduce Delta 0 to 100% 6
DS.RD Dig Scroll Reduce Delay 15 to 60 sec 30
DS.RO Dig Scroll Reduction OAT 70 to 120 dF 95
DS.MO Dig Scroll Max Only OAT 70 to 120 dF 105
MLV Min Load Valve Enable Enable/Disable Disable
H.SST Hi SST Alert Delay Time 5 to 30 min 10
RR.VF Rev Rotation Verified? Yes/No No
CS.HP Use CSBs for HPS detect? Yes/No Yes
EDT.R EVAP.DISCHRGE TEMP RESET
RS.CF EDT Reset Configuration 0 to 3 (multi-text strings) 2
RTIO Reset Ratio 0 to 10 3
LIMT Reset Limit 0 to 20 ^F 10
RES.S EDT 4-20 ma Reset Input Enable/Disable Disable
HEAT HEATING CONFIGURATION
HT.CF Heating Control Type 0 to 5 0
HT.SP Heating Supply Air Setpt 80 to 120 dF 85
OC.EN Occupied Heating Enabled Yes/No No
LAT.M MBB Sensor Heat Relocate Yes/No No
SG.CF STAGED HEAT CONFIGS
SG.CFHT.ST Staged Heat Type 0 to 5 0
SG.CFCAP.M Max Cap Change per Cycle 5 to 45 45
SG.CFM.R.DB S.Gas DB min.dF/PID Rate 0 to 5 0.5
SG.CFS.G.DB St.Gas Temp. Dead Band 0 to 5 ^F 2
SG.CFRISE Heat Rise dF/sec Clamp 0.05 to 0.2 0.06
SG.CFLAT.L LAT Limit Config 0 to 20 ^F 10
SG.CFLIM.M Limit Switch Monitoring? Yes/No Yes
SG.CF
SW.H.T Limit Switch High Temp 80 to 210 dF 170
SG.CFSW.L.T Limit Switch Low Temp 80 to 210 dF 160
SG.CFHT.P Heat Control Prop. Gain 0 to 1.5 1
SG.CFHT.D Heat Control Derv. Gain 0 to 1.5 1
SG.CFHT.TM Heat PID Rate Config 60 to 300 sec 90
HH.CF HYDRONIC HEAT CONFIGS
HH.CFHW.P Hydronic Ctl.Prop. Gain 0 to 1.5 1
HH.CFHW.I Hydronic Ctl.Integ. Gain 0 to 1.5 1
HH.CFHW.D Hydronic Ctl.Derv. Gain 0 to 1.5 1
HH.CFHW.TM Hydronic PID Rate Config 15 to 300 sec 90
HH.CFACT.C HYDR.HEAT ACTUATOR CFGS.
HH.CFACTCSN.1 Hydronic Ht.Serial Num.1 0 to 9999 0
HH.CFACTCSN.2 Hydronic Ht.Serial Num.2 0 to 6 0
HH.CFACTCSN.3 Hydronic Ht.Serial Num.3 0 to 9999 0
HH.CFACTCSN.4 Hydronic Ht.Serial Num.4 0 to 254 0
HH.CFACTCC.A.LM Hydr.Ht.Ctl.Ang.Lo Limit 0 to 90 85
SP SUPPLY STATIC PRESS.CFG.
SP.CF Static Pressure Config Enable/Disable Disable
SP.SV Staged Air Volume Control Enable/Disable Disable
SP.S Static Pressure Sensor Enable/Disable Disable
SP.LO Static Press. Low Range –10 to 0 in. wg 0
SP.HI Static Press. High Range 0 to 10 in. wg 5
SP.SP Static Pressure Setpoint 0 to 5 in. wg 1.5
SP.MN VFD Minimum Speed 0 to 100% 20
SP.MX VFD Maximum Speed 0 to 100% 100
HS.MN VFD MinSpeed in HeatMode 0 to 100 75
HS.MX VFD MaxSpeed in HeatMode 0 to 100 100
SP.FS VFD Fire Speed Over. 0 to 100% 100
SP.RS Stat. Pres. Reset Config 0 to 4 (multi-text strings) 0
SP.RT SP Reset Ratio 0.00 to 2.00 0.20
SP.LM SP Reset Limit 0.00 to 2.00 0.75
SP.EC SP Reset Econo Position 0 to 100% 5
S.PID STAT.PRESS.PID CONFIGS
S.PIDSP.TM Stat.Pres.PID Run Rate 5 to 120 sec 15
S.PIDSP.P Static Press. Prop. Gain 0 to 5 0.5
S.PIDSP.I Static Pressure Intg. Gain 0 to 2 0.5
S.PIDSP.D Static Pressure Derv. Gain 0 to 5 0.3