CL-8
-
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -- - - - - - - - - - - - - - - - - - - -
CUT ALONG DOTTED LINE CUT ALONG DOTTED LINE
CONTROLS SET POINT AND CONFIGURATION LOG (cont)
ITEM EXPANSION RANGE DEFAULT SETTING
ECON ECONOMIZER CONFIGURATION
EC.EN Economizer Installed? Yes/No Yes
EC2.E Econ.Act.2 Installed? Yes/No No
EC.MN Economizer Min.Position 0 to 100% 5
EC.MX Economizer Max.Position 0 to 100% 98
E.SEL Econ ChangeOver Select 0 to 3 (multi-text strings) 0
DDB.C Diff Dry Bulb RAT Offset 0 to 3 0
E.TRM Economzr Trim For SumZ? Yes/No Yes
OA.E.C OA Enthalpy ChgOvr Selct 1 to 5 (multi-text strings) 4
OA.EN Outdr.Enth Compare Value 18 to 28 24
OAT.L High OAT Lockout Temp –40 to 120 dF 60
O.DEW OA Dewpoint Temp Limit 50 to 62 dF 55
ORH.S Outside Air RH Sensor Enable/Disable Disable
CFM.C OUTDOOR AIR CFM CONTROL
CFM.COCF.S Outdoor Air CFM Sensor Enable/Disable Disable
CFM.CO.C.MX Economizer Min.Flow 0 to 20000 CFM 2000
CFM.CO.C.MN IAQ Demand Vent Min.Flow 0 to 20000 CFM 0
CFM.CO.C.DB Econ.Min.Flow Deadband 200 to 1000 CFM 400
E.CFG ECON.OPERATION CONFIGS
E.CFGE.P.GN Economizer Prop.Gain 0.7 to 3.0 1
E.CFGE.RNG Economizer Range Adjust 0.5 to 5 ^F 2.5
E.CFGE.SPD Economizer Speed Adjust 0.1 to 10 0.75
E.CFGE.DBD Economizer Deadband 0.1 to 2 ^F 0.5
UEFC UNOCC.ECON.FREE COOLING
UEFCFC.CF Unoc Econ Free Cool Cfg 0 to 2 (multi-text strings) 0
UEFCFC.TM Unoc Econ Free Cool Time 0 to 720 min 120
UEFC
FC.L.O Un.Ec.Free Cool OAT Lock 40 to 70 dF 50
ACT.C ECON.ACTUATOR CONFIGS
ACTCSN.1.1 Econ Serial Number 1 0 to 9999 0
ACTCSN.1.2 Econ Serial Number 2 0 to 6 0
ACTCSN.1.3 Econ Serial Number 3 0 to 9999 0
ACTCSN.1.4 Econ Serial Number 4 0 to 254 0
ACTCC.A.L1 Econ Ctrl Angle Lo Limit 0 to 90 85
ACTCSN.2.1 Econ 2 Serial Number 1 0 to 9999 0
ACTCSN.2.2 Econ 2 Serial Number 2 0 to 6 0
ACTCSN.2.3 Econ 2 Serial Number 3 0 to 9999 0
ACTCSN.2.4 Econ 2 Serial Number 4 0 to 254 0
ACTCC.A.L2 Econ 2 Ctrl Angle Lo Limit 0 to 90 85
T.24.C TITLE 24 CONFIGS
T.24.CLOG.F Log Title 24 Faults Yes/No No
T.24.CEC.MD T24 Econ Move Detect 1 to 10 1
T.24.CEC.ST T24 Econ Move SAT Test 10 to 20 10
T.24.CS.CHG T24 Econ Move SAT Change 0 to 5 0.2
T.24.CE.SOD T24 Econ RAT-OAT Diff 5 to 20 15
T.24.CE.CHD T24 Heat/Cool End Delay 0 to 60 25
T.24.CSAT.T SAT Settling Time 10 to 900 240
T.24.CET.MN T24 Test Minimum Pos. 0 to 50 15
T.24.C
ET.MX T24 Test Maximum Pos. 50 to 100 85
T.24.CAC.EC Economizer Deadband Temp 0 to 10 4
T.24.CE.GAP Econ Fault Detect Gap 2 to 100 5
T.24.CE.TMR Econ Fault Detect Timer 10 to 240 20
T.24.CX.CFM Excess Air CFM 400 to 4000 800
T.24.CX.TMR Excess Air Detect Timer 30 to 240 150
T.24.CAC.MR T24 AutoTest SF Run Time 1 to 10 2
T.24.CAC.SP T24 Auto-Test VFD Speed 10 to 50 20
T.24.CAC.OP T24 Auto-Test Econ % Opn 1 to 100 50
T.24.CVF.PC T24 Auto-Test VFD % Chng 1 to 20 10
T.24.CEC.DY T24 Econ Auto-Test Day
0=Never,
1=Monday,
2=Tuesday,
3=Wednesday,
4=Thursday,
5=Friday,
6=Saturday,
7=Sunday
6=Saturday
T.24.CEC.TM T24 Econ Auto-Test Time 0 to 23 2
EP.MS ECON POS AT MIN VFD SPEED
EP.XS ECON POS AT MAX VFD SPEED