APPENDIX A — LOCAL DISPLAY TABLES
Table B — MODE — SERVICE TEST
ITEM EXPANSION RANGE UNITS CCN POINT WRITE STATUS PAGE NO.
TEST Service Test Mode ON/OFF MAN_CTRL 37
STOP Local Machine Disable YES/NO UNITSTOP config 37
S.STP Soft Stop Request YES/NO SOFTSTOP forcible 37
FAN.F Supply Fan Request YES/NO SFANFORC forcible 37
INDP TEST INDEPENDENT OUTPUTS
HUM.R Humidifier Relay ON/OFF HUMR_TST 37
ALRM Remote Alarm / Aux Relay ON/OFF ALRM_TST 37
FANS TEST FANS
F.MOD Fan Test Automatic? YES/NO FANAUTO 36,37
E.POS Econo Damper Command Pos % ECONFANS 37
S.FAN Supply Fan Relay ON/OFF SFAN_TST 37
S.VFD Supply Fan VFD Speed 0-100 % SFVFDTST 37
P.E.1 Power Exhaust Relay 1 ON/OFF PE1_TST 37
E.VFD Exhaust Fan VFD Speed 0-100 % EFVFDTST 37
P.E.2 Power Exhaust Relay 2 ON/OFF PE2_TST 37
BP1.C BP 1 Command Position 0-100 % BLDPTST1 37
BP2.C BP 2 Command Position 0-100 % BLDPTST2 37
CDF.1 Condenser Fan Output 1 ON/OFF CDF1_TST 37
CDF.2 Condenser Fan Output 2 ON/OFF CDF2_TST 37
CDF.3 Condenser Fan Output 3 ON/OFF CDF3_TST 37
CDF.4 Condenser Fan Output 4 ON/OFF CDF4_TST 37
ACT.C CALIBRATE TEST-ACTUATORS
ECN.C Economizer Act.Cmd.Pos. 0-100 % ECON1TST 37
EC.CL Economizer Calibrate Cmd YES/NO ECONOCAL 37
ECN.A Econ Act. Control Angle read only ECONCANG 37
EC2.C Economzr 2 Act.Cmd.Pos. 0-100 % ECON2TST 37
E2.CL Economzr 2 Calibrate Cmd YES/NO ECON2CAL 37
EC2.A Econ2 Act. Control Angle read only ECN2CANG 37
BP1.C BP 1 Command Position 0-100 % BLDG1TST 37
B1.CL BP 1 Actuator Cal Cmd YES/NO BLDG1CAL 37
BP1.A BP Act.1 Control Angle read only BP1_CANG 37
BP1.M BP 1 Actuator Max Pos. 0-100 % BP1SETMX 37
BP2.C BP 2 Command Position 0-100 % BLDG2TST 37
B2.CL BP 2 Actuator Cal Cmd YES/NO BLDG2CAL 37
BP2.A BP Act.2 Control Angle read only BP2_CANG 36
BP2.M BP 2 Actuator Max Pos. 0-100 % BP2SETMX 37
HTC.C Ht.Coil Command Position 0-100 % HTCLACTC 37
HT.CL Heating Coil Act. Cal.Cmd YES/NO HCOILCAL 37
HTC.A Heat Coil Act.Ctl.Angle read only HTCLCANG 37
HMD.C Humidifier Command Pos. 0-100 % HUMD_TST 37
HM.CL Humidifier Act. Cal.Cmd YES/NO HUMIDCAL 37
HMD.A Humidifier Act.Ctrl.Ang. read only HUMDCANG 37
HMZR TEST HUMIDIMIZER
RHV HumidiMiZer 3-way Valve Off/On RHVH_TST 37,38
C.EXV Condenser EXV Position 0 to 100 % CEXVHTST 37,38
B.EXV Bypass EXV Position 0 to 100 % BEXVHTST 37,38
C.CAL Condenser EXV Calibrate Off/On CEXV_CAL 37,38
B.CAL Bypass EXV Calibrate Off/On BEXV_CAL 37,38
COOL TEST COOLING
E.POS Econo Damper Command Pos 0-100 % ECONCOOL 37,38
SP.SP Static Pressure Setpoint 0-5 " H2O SPSP_TST 37,38
CL.ST Requested Cool Stage 0-n CLST_TST 37,38
MLV Minimum Load Valve Relay ON/OFF MLV_TST 37
A1 Compressor A1 Relay ON/OFF CMPA1TST 37
A1.CP Compressor A1 Capacity 20-100 A1CAPTST 37
A1.B1 Two Circuit Start A1,B1 ON/OFF CMPABTST 37
A2 Compressor A2 Relay ON/OFF CMPA2TST 37
A3 Compressor A3 Relay ON/OFF CMPA3TST 37
B1 Compressor B1 Relay ON/OFF CMPB1TST 37
B2 Compressor B2 Relay ON/OFF CMPB2TST 37
B3 Compressor B3 Relay ON/OFF CMPB3TST 37
RHV HumidiMiZer 3-way Valve Off/On RHVH_TST 37-38
C.EXV Condenser EXV Position 0 to 100 % CEXVHTST 37-38
B.EXV Bypass EXV Position 0 to 100 % BEXVHTST 37-38
HEAT TEST HEATING
HT.ST Requested Heat Stage 0-n HTST_TST 37,39
HT.1 Heat Relay 1 ON/OFF HS1_TST 37,39
H1.CP Modulating Heat Capacity 0-100 % MGAS_TST 37,39
HT.2 Heat Relay 2 ON/OFF HS2_TST 37,39
HT.3 Relay 3 W1 Gas Valve 2 ON/OFF HS3_TST 37,39
HT.4 Relay 4 W2 Gas Valve 2 ON/OFF HS4_TST 37,39
HT.5 Relay 5 W1 Gas Valve 3 ON/OFF HS5_TST 37,39
HT.6 Relay 6 W2 Gas Valve 3 ON/OFF HS6_TST 37,39
H.I.R Heat Interlock Relay ON/OFF HIR_TST 37,39
HTC.C Ht.Coil Command Position 0-100 % HTCLHEAT 37,39