ACTCC.A.L2 Ecn2 Ctrl Angle Lo Limit 0 to 90 ECN2CALM 85 76, 78
T.24.C TITLE 24 CONFIGS
T.24.CLOG.F Log Title 24 Faults Yes/No T24LOGFL No 74, 76
T.24.CEC.MD T24 Econ Move Detect 1 to 10 T24ECMDB 1 74, 76
T.24.CEC.ST T24 Econ Move SAT Test 10 to 20 T24ECSTS 10 74, 76
T.24.CS.CHG T24 Econ Move SAT Change 0 to 5 T24SATMD 0.2 75, 76
T.24.CE.SOD T24 Econ RAT-OAT Diff 5 to 20 T24RATDF 15 75, 76
T.24.CE.CHD T24 Heat/Cool End Delay 0 to 60 T24CHDLY 25 75, 76
T.24.CSAT.T SAT Settling Time 10 to 900 SAT_SET 240 75, 76
T.24.CET.MN T24 Test Minimum Pos. 0 to 50 T24TSTMN 15 75, 76
T.24.CET.MX T24 Test Maximum Pos. 50 to 100 T24TSTMX 85 75, 76
T.24.CAC.EC Economizer Deadband Temp 0 to 10 AC_EC_DB 4 75, 76
T.24.CE.GAP Econ Fault Detect Gap 2 to 100 EC_FLGAP 5 75, 76
T.24.CE.TMR Econ Fault Detect Timer 10 to 240 EC_FLTMR 20 75, 76
T.24.CX.CFM Excess Air CFM 400 to 4000 EX_ARCFM 800 75, 76
T.24.CX.TMR Excess Air Detect Timer 30 to 240 EX_ARTMR 150 75, 76
T.24.CAC.MR T24 AutoTest SF Run Time 1 to 10 T24ACMRT 2 75, 76
T.24.CAC.SP T24 Auto-Test VFD Speed 10 to 50 T24ACSPD 20 75, 76
T.24.CAC.OP T24 Auto-Test Econ % Opn 1 to 100 T24ACOPN 50 75, 76
T.24.CVF.PC T24 Auto-Test VFD % Chng 1 to 20 T24VFDPC 10 75, 76
T.24.C
EC.DY T24 Econ Auto-Test Day 0=Never,
1=Monday,
2=Tuesday,
3=Wednesday,
4=Thursday,
5=Friday,
6=Saturday,
7=Sunday
T24_ECDY 6=Saturday 75, 76
T.24.CEC.TM T24 Econ Auto-Test Time 0 to 23 T24_ECTM 2 75, 76
BP BUILDING PRESS. CONFIGS
BP.CF Building Press. Config 0 to 5 (multi-text strings) BLDG_CFG 0 34, 35, 80, 81, 82, 83, 98, 127
BP.S Building Pressure Sensor Enable/Disable BPSENS Disable 80, 81
BP.R Bldg. Press. (+/-) Range 0.10 to 0.25 " H2O BP_RANGE 0.25 80, 81
BP.SP Building Pressure Setp. -0.25 to 0.25 " H2O BPSP 0.05 34, 35, 81
BP.SO BP Setpoint Offset 0 to 0.5 " H2O BPSO 0.05 34, 81
BP.P1 Power Exhaust On Setp.1 0 to 100 % PES1 25 34, 81, 82
BP.P2 Power Exhaust On Setp.2 0 to 100 % PES2 75 34, 81, 82
B.V.A VFD/ACTUATOR CONFIG
B.V.ABP.FS VFD/Act. Fire Speed/Pos. 0 to 100 % BLDGPFSO 100 34, 35, 81, 84
B.V.ABP.MN VFD/Act. Min.Speed/Pos. 0 to 50 % BLDGPMIN 0 34, 35, 81
B.V.ABP.MX VFD Maximum Speed 50 to 100 % BLDGPMAX 100 34, 35, 81
B.V.ABP.1M BP 1 Actuator Max Pos. 85 to 100 % BP1SETMX 100 34, 81
B.V.ABP.2M BP 2 Actuator Max Pos. 85 to 100 % BP2SETMX 100 34, 81
B.V.ABP.CL BP Hi Cap VFD Clamp Val. 5 to 25 % BLDGCLMP 10 34, 81
FAN.T FAN TRACKING CONFIG
FAN.TFT.CF Fan Track Learn Enable Yes/No DCFM_CFG No 35, 82
FAN.TFT.TM Fan Track Learn Rate 5-60 min DCFMRATE 15 35, 81
FAN.TFT.ST Fan Track Initial DCFM -20000 to 20000 CFM DCFMSTRT 2000 35, 81, 82
FAN.TFT.MX Fan Track Max Clamp 0 to 20000 CFM DCFM_MAX 4000 35, 81, 82
FAN.TFT.AD Fan Track Max Correction 0 -20000 CFM DCFM_ADJ 1000 35, 81, 82
FAN.TFT.OF
Fan Track Internl EEPROM -20000 to 20000 CFM DCFM_OFF 0 35, 81, 82
FAN.TFT.RM Fan Track Internal RAM -20000 to 20000 CFM DCFM_RAM 0 35, 81, 82
FAN.TFT.RS Fan Track Reset Internal Yes/No DCFMRSET No 35, 81, 82
FAN.TSCF.C Supply Air CFM Config 1 to 2 (multi-text strings) SCFM_CFG 1 35, 81, 82
B.PID BLDG.PRESS.PID CONFIGS
B.PIDBP.TM Bldg.Pres.PID Run Rate 5 to 120 sec BPIDRATE 10 81, 82
B.PIDBP.P Bldg.Press. Prop. Gain 0 to 5 BLDGP_PG 0.5 81, 82
B.PIDBP.I Bldg.Press. Integ. Gain 0 to 2 BLDGP_IG 0.5 81, 82
B.PIDBP.D Bldg.Press. Deriv. Gain 0 to 5 BLDGP_DG 0.3 81, 82
ACT.C BLDG.PRES. ACTUATOR CFGS
ACT.CBP.1 BLDG.PRES. ACT.1 CONFIGS 81, 83
ACT.CBP.1SN.1 BP 1 Serial Number 1 0 to 9999 BP_1_SN1 0 81, 83
ACT.CBP.1SN.2 BP 1 Serial Number 2 0 to 6 BP_1_SN2 0 81, 83
ACT.CBP.1SN.3 BP 1 Serial Number 3 0 to 9999 BP_1_SN3 0 81, 83
ACT.CBP.1SN.4 BP 1 Serial Number 4 0 to 254 BP_1_SN4 0 81, 83
ACT.CBP.1C.A.LM BP1 Cntrl Angle Lo Limit 0-90 BP1_CALM 35 81, 83
ACT.CBP.2 BLDG.PRES. ACT.2 CONFIGS
ACT.CBP.2SN.1 BP 2 Serial Number 1 0 to 9999 BP_2_SN1 0 81, 83
ACT.CBP.2SN.2
BP 2 Serial Number 2 0 to 6 BP_2_SN2 0 81, 83
ACT.CBP.2SN.3 BP 2 Serial Number 3 0 to 9999 BP_2_SN3 0 81, 83
ACT.CBP.2SN.4 BP 2 Serial Number 4 0 to 254 BP_2_SN4 0 81, 83
ACT.CBP.2C.A.LM BP2 Cntrl Angle Lo Limit 0-90 BP2_CALM 35 81, 83
D.LV.T COOL/HEAT SETPT. OFFSETS
L.H.ON Dmd Level Lo Heat On -1 to 2 ^F DMDLHON 1.5 33, 50, 61
H.H.ON Dmd Level(+) Hi Heat On 0.5 to 20.0 ^F DMDHHON 0.5 50, 61
L.H.OF Dmd Level(-) Lo Heat Off 0.5 to 2.0 ^F DMDLHOFF 1 33, 50, 61, 62
APPENDIX A — LOCAL DISPLAY TABLES
Table H — MODE — CONFIGURATION (cont)
ITEM EXPANSION RANGE UNITS CCN POINT DEFAULT PAGE NO.