SG.CFLAT.L LAT Limit Config 0 to 20 ^F HTLATLIM 10 60, 63, 64, 67
SG.CFLIM.M Limit Switch Monitoring? Yes/No HTLIMMON Yes 60, 63, 64, 65, 67
SG.CFSW.H.T Limit Switch High Temp 80 to 210 dF HT_LIMHI 170 60, 63, 64, 65, 67
SG.CFSW.L.T Limit Switch Low Temp 80 to 210 dF HT_LIMLO 160 60, 63, 64, 65, 67
SG.CFHT.P Heat Control Prop. Gain 0 to 1.5 HT_PGAIN 1 60, 63, 64
SG.CFHT.D Heat Control Derv. Gain 0 to 1.5 HT_DGAIN 1 60, 63, 64
SG.CFHT.TM Heat PID Rate Config 30 to 300 sec HTSGPIDR 90 60, 63, 64
HH.CF HYDRONIC HEAT CONFIGS
HH.CFHW.P Hydronic Ctl.Prop. Gain 0 to 1.5 HW_PGAIN 1 60, 62, 63
HH.CFHW.I Hydronic Ctl.Integ. Gain 0 to 1.5 HW_IGAIN 1 60, 62, 63
HH.CFHW.D Hydronic Ctl.Derv. Gain 0 to 1.5 HW_DGAIN 1 60, 62, 63
HH.CFHW.TM Hydronic PID Rate Config 15 to 300 sec HOTWPIDR 90 60, 62, 63
HH.CFACT.C HYDR.HEAT ACTUATOR CFGS.
HH.CFACTCSN.1 Hydronic Ht.Serial Num.1 0 to 9999 HTCL_SN1 0 60, 62, 63
HH.CFACTCSN.2 Hydronic Ht.Serial Num.2 0 to 6 HTCL_SN2 0 60, 62, 63
HH.CFACTCSN.3 Hydronic Ht.Serial Num.3 0 to 9999 HTCL_SN3 0 60, 62, 63
HH.CFACTCSN.4 Hydronic Ht.Serial Num.4 0 to 254 HTCL_SN4 0 60, 62, 63
HH.CFACTCC.A.LM Hydr.Ht.Ctl.Ang.Lo Limit 0-90 HTCLCALM 85 60, 62
SP SUPPLY STATIC PRESS.CFG.
SP.CF Static Pressure Config Enable/Disable STATICFG Disable 39, 69, 70, 72
SP.SV Staged Air Volume Control Enable/Disable STGAVCFG Disable 69, 70
SP.S Static Pressure Sensor Enable/Disable SPSENS Disable 69, 70
SP.LO Static Press. Low Range -10 to 0 in. W.C. SP_LOW 0 70
SP.HI Static Press. High Range 0 to 10 in. W.C. SP_HIGH 5 70
SP.SP Static Pressure Setpoint 0 to 5 in. W.C. SPSP 1.5 33, 69, 70, 71
SP.MN VFD Minimum Speed 0 to 100 % STATPMIN 20 39, 70
SP.MX VFD Maximum Speed 0 to 100 % STATPMAX 100 39, 70
SP.FS VFD Fire Speed Over. 0 to 100 % STATPFSO 100 70, 84
SP.RS Stat. Pres. Reset Config 0 to 4 (multi-text strings) SPRSTCFG 0 39, 45, 70, 71, 72
SP.RT SP Reset Ratio 0.00 to 2.00 SPRRATIO 0.20 70
SP.LM SP Reset Limit 0.00 to 2.00 SPRLIMIT 0.75 70, 71
SP.EC SP Reset Econo. Position 0 to 100 % ECONOSPR 5 70, 71
S.PID STAT.PRESS.PID CONFIGS
S.PIDSP.TM Stat.Pres.PID Run Rate 5 to 120 sec SPIDRATE 15 70, 71
S.PIDSP.P Static Press. Prop. Gain 0 to 5 STATP_PG 0.5 70, 71
S.PIDSP.I Static Pressure Intg. Gain 0 to 2 STATP_IG 0.5 70, 71
S.PIDSP.D Static Pressure Derv. Gain 0 to 5 STATP_DG 0.3 70, 71
ECON ECONOMIZER CONFIGURATION
EC.EN Economizer Installed? Yes/No ECON_ENA Yes 34, 75, 76
EC2.E Econ.Act.2 Installed? Yes/No ECON_TWO No 34, 75, 76
EC.MN Economizer Min.Position 0 to 100 % ECONOMIN 5 34, 75, 76, 79, 125
EC.MX Economizer Max.Position 0 to 100 % ECONOMAX 98 34, 56, 75, 76
E.TRM Economzr Trim For SumZ ? Yes/No ECONTRIM Yes 34, 54, 75, 76
E.SEL Econ ChangeOver Select 0 to 3 (multi-text strings) ECON_SEL 0 34, 41, 73, 74, 76, 77
DDB.C Diff Dry Bulb RAT Offset 0 to 3 dF EC_DDBCO 0 74, 76
OA.E.C OA Enthalpy ChgOvr Selct 1 to 5 (multi-text strings) OAEC_SEL 4 34, 76, 77
OA.EN Outdr.Enth Compare Value 18 to 28 OAEN_CFG 24 34, 76, 77
OAT.L High OAT Lockout Temp -40 to 120 dF OAT_LOCK 60 34, 76, 77
O.DEW OA Dewpoint Temp Limit 50 to 62 dF OADEWCFG 55 34, 76, 78
ORH.S Outside Air RH Sensor Enable/Disable OARHSENS Disable 34, 45, 76, 77, 95
CFM.C
OUTDOOR AIR CFM CONTROL
CFM.COCF.S Outdoor Air CFM Sensor Enable/Disable OCFMSENS Disable 34, 45, 73, 76, 79, 87
CFM.CO.C.MX Economizer Min.Flow 0 to 20000 CFM OACFMMAX 2000 34, 76, 79, 87
CFM.CO.C.MN IAQ Demand Vent Min.Flow 0 to 20000 CFM OACFMMIN 0 34, 76, 79, 87
CFM.CO.C.DB Econ.Min.Flow Deadband 200 to 1000 CFM OACFM_DB 400 34, 76, 79, 87
E.CFG ECON.OPERATION CONFIGS
E.CFGE.P.GN Economizer Prop.Gain 0.7 to 3.0 EC_PGAIN 1 76
E.CFGE.RNG Economizer Range Adjust 0.5 to 5 ^F EC_RANGE 2.5 76
E.CFGE.SPD Economizer Speed Adjust 0.1 to 10 EC_SPEED 0.75 76
E.CFGE.DBD Economizer Deadband 0.1 to 2 ^F EC_DBAND 0.5 76
UEFC UNOCC.ECON.FREE COOLING
UEFCFC.CF Unoc Econ Free Cool Cfg 0-2 (multi-text strings) UEFC_CFG 0 76, 78
UEFCFC.TM Unoc Econ Free Cool Time 0 to 720 min UEFCTIME 120 76, 78
UEFCFC.L.O Un.Ec.Free Cool OAT Lock 40 to 71 dF UEFCNTLO 50 76
ACT.C ECON.ACTUATOR CONFIGS
ACTCSN.1.1 Econ Serial Number 1 0 to 9999 ECON_SN1 0 76
ACTCSN.1.2 Econ Serial Number 2 0 to 6 ECON_SN2 0 76
ACTCSN.1.3 Econ Serial Number 3 0 to 9999 ECON_SN3 0 76
ACTCSN.1.4 Econ Serial Number 4 0 to 254 ECON_SN4 0 76
ACTCC.A.L1 Econ Ctrl Angle Lo Limit 0 to 90 ECONCALM 85 76, 78
ACTCSN.2.1 Econ 2 Serial Number 1 0 to 9999 ECN2_SN1 0 76
ACTCSN.2.2 Econ 2 Serial Number 2 0 to 6 ECN2_SN2 0 76
ACTCSN.2.3 Econ 2 Serial Number 3 0 to 9999 ECN2_SN3 0 76
ACTCSN.2.4 Econ 2 Serial Number 4 0 to 254 ECN2_SN4 0 76
APPENDIX A — LOCAL DISPLAY TABLES
Table H — MODE — CONFIGURATION (cont)
ITEM EXPANSION RANGE UNITS CCN POINT DEFAULT PAGE NO.