APPENDIX B — CCN TABLES
Table O — SERVICE-CONFIG TABLES (cont)
TABLE DISPLAY NAME RANGE UNITS POINT NAME DEFAULT
ALLM
SPT lo alert limit/occ -10-245 dF SPLO 60
SPT hi alert limit/occ -10-245 dF SPHO 85
SPT lo alert limit/unocc -10-245 dF SPLU 45
SPT hi alert limit/unocc -10-245 dF SPHU 100
EDT lo alert limit/occ -40-245 dF SALO 40
EDT hi alert limit/occ -40-245 dF SAHO 100
EDT lo alert limit/unocc -40-245 dF SALU 40
EDT hi alert limit/unocc -40-245 dF SAHU 100
RAT lo alert limit/occ -40-245 dF RALO 60
RAT hi alert limit/occ -40-245 dF RAHO 90
RAT lo alert limit/unocc -40-245 dF RALU 40
RAT hi alert limit/unocc -40-245 dF RAHU 100
OAT lo alert limit -40-245 dF OATL -40
OAT hi alert limit -40-245 dF OATH 150
RARH low alert limit 0-100 % RRHL 0
RARH high alert limit 0-100 % RRHH 100
OARH low alert limit 0-100 % ORHL 0
OARH high alert limit 0-100 % ORHH 100
SP low alert limit 0-5 " H2O SPL 0
SP high alert limit 0-5 " H2O SPH 2
BP lo alert limit -0.25-0.25 " H2O BPL -0.25
BP high alert limit -0.25-0.25 " H2O BPH 0.25
IAQ high alert limit 0-5000 IAQH 1200
BP__
Building Press. Config 0-5 BLDG_CFG 0
Building Pressure Sensor Enable/Disable BPSENS Disable
Bldg. Press. (+/-) Range 0.10 to 0.25 " H2O BP_RANGE 0.25
Building Pressure Setp. -0.25 to 0.25 " H2O BPSP 0.05
BP Setpoint Offset 0 to 0.5 ^" H2O BPSO 0.05
Power Exhaust On Setp.1 0 to 100 % PES1 25
Power Exhaust On Setp.2 0 to 100 % PES2 75
VFD/Act. Fire Speed/Pos. 0 to 100 % BLDGPFSO 100
VFD/Act. Min. Speed/Pos. 0 to 100 % BLDGPMIN 10
VFD Maximum Speed 0 to 100 % BLDGPMAX 100
BP 1 Actuator Max Pos. 85 to 100 % BP1SETMX 100
BP 2 Actuator Max Pos. 85 to 100 % BP2SETMX 100
BP Hi Cap VFD Clamp Val. 5 to 25 % BLDGCLMP 10
Fan Track Learn Enable Yes/No DCFM_CFG NO
Fan Track Learn Rate 5-60 min DCFMRATE 15
Fan Track Initial DCFM -20000 to 20000 CFM DCFMSTRT 2000
Fan Track Max Clamp 0 to 20000 CFM DCFM_MAX 4000
Fan Track Max Correction 0 -20000 CFM DCFM_ADJ 1000
Fan Track Internl EEPROM -20000 to 20000 CFM DCFM_OFF 0
Fan Track Internal RAM -20000 to 20000 CFM DCFM_RAM 0
Fan Track Reset Internal Yes/No DCFMRSET No
Supply Air CFM Config 1 to 2 (multi-text strings) SCFM_CFG 1
Bldg.Pres.PID Run Rate 5 to 120 sec BPIDRATE 10
Bldg.Press. Prop. Gain 0 to 5 BLDGP_PG 1
Bldg.Press. Integ. Gain 0 to 2 BLDGP_IG 1
Bldg.Press. Deriv. Gain 0 to 5 BLDGP_DG 0.5
BP 1 Serial Number 1 0 to 9999 BP_1_SN1 0
BP 1 Serial Number 2 0 to 6 BP_1_SN2 0
BP 1 Serial Number 3 0 to 9999 BP_1_SN3 0
BP 1 Serial Number 4 0 to 254 BP_1_SN4 0
BP1 Cntrl Angle Lo Limit 0-90 BP1_CALM 35
BP 2 Serial Number 1 0 to 9999 BP_2_SN1 0
BP 2 Serial Number 2 0 to 6 BP_2_SN2 0
BP 2 Serial Number 3 0 to 9999 BP_2_SN3 0
BP 2 Serial Number 4 0 to 254 BP_2_SN4 0