BP__ (cont) BP2 Cntrl Angle Lo Limit 0-90 BP2_CALM 35
COOL
Enable Compressor A1 Enable/Disable CMPA1ENA Enable
Enable Compressor A2 Enable/Disable CMPA2ENA Enable
Enable Compressor A3 Enable/Disable CMPA3ENA Enable
Enable Compressor B1 Enable/Disable CMPB1ENA Enable
Enable Compressor B2 Enable/Disable CMPB2ENA Enable
Enable Compressor B3 Enable/Disable CMPB3ENA Enable
CSB A1 Feedback Alarm Enable/Disable CSB_A1EN Enable
CSB A2 Feedback Alarm Enable/Disable CSB_A2EN Enable
CSB A3 Feedback Alarm Enable/Disable CSB_A3EN Enable
CSB B1 Feedback Alarm Enable/Disable CSB_B1EN Enable
CSB B2 Feedback Alarm Enable/Disable CSB_B2EN Enable
CSB B3 Feedback Alarm Enable/Disable CSB_B3EN Enable
Capacity Threshold Adjst -10 to 10 Z_GAIN 1
Compressor Lockout Temp -25 to 55 dF OATLCOMP 40
Lead/Lag Configuration LEAD_LAG
Motor Master Control ? Yes/No MOTRMAST No
Maximum Condenser Temp dF SCT_MAX
Minimum Condenser Temp dF SCT_MIN
A1 is a Digital Scroll Yes/No DIGCMPA1
A1 Min Digital Capacity % MINCAPA1
Dig Scroll Adjust Delta % DSADJPCT
Dig Scroll Adjust Delay sec DSADJDLY
Dig Scroll Reduce Delta % DSREDPCT
Dig Scroll Reduce Delay sec DSREDDLY
Dig Scroll Reduction OAT dF DSREDOAT
Dig Scroll Max Only OAT dF DSMAXOAT
Min Load Valve Enable Enable/Disable MLV_ENAB
Hi SST Alert Delay Time 5 to 30 min HSSTTIME 10
Rev Rotation Verified ? Yes/No REVR_VER
Use CSBs for HPS Detect Yes/No CSBHPDET
DEHU
Dehumidification Config 0-3 DHSELECT 0
Dehumidification Sensor 1-3 DHSENSOR 1
Econ disable in DH mode? Yes/No DHECONEN No
Vent Reheat Setpt Select 0-1 DHVHTCFG 0
Vent Reheat RAT offset 0-8 ^F DHVRAOFF 0
Vent Reheat Setpoint 55-95 dF DHVHT_SP 70
Dehumidify Cool Setpoint 40-55 dF DHCOOLSP 45
Dehumidify RH Setpoint 10-90 % DHRELHSP 55
Humidimizer Adjust Rate secs HMZRRATE
Humidimizer Prop. Gain HMZR_PG
Bypass EXV Max Open % BYP_MAX
Condenser EXV Max Open % COND_MAX
LAT Sample Buffer Length LAT_SAMP
LAT Sample Rate seconds secs LAT_RATE
DISP
Metric Display Off/On DISPUNIT Off
Language Selection 0-1 LANGUAGE 0
Password Enable Enable/Disable PASS_EBL Enable
Service Password 0000-9999 PASSWORD 1111
Contrast Adjustment 0-255 CNTR_ADJ 0
Brightness Adjustment 0-255 BRTS_ADJ 0
DLVT
Dmd Level Lo Heat On -1 to 2 ^F DMDLHON 1.5
Dmd Level(+) Hi Heat On 0.5 to 20.0 ^F DMDHHON 0.5
Dmd Level(-) Lo Heat Off 0.5 to 2.0 ^F DMDLHOFF 1
Dmd Level Lo Cool On -1 to 2 ^F DMDLCON 1.5
Dmd Level(+) Hi Cool On 0.5 to 20.0 ^F DMDHCON 0.5