201
DLVT (cont) Dmd Level(-) Lo Cool Off 0.5 to 2.0 ^F DMDLCOFF 1
Cool Trend Demand Level 0.1 to 5.0 ^F CTRENDLV 0.1
Heat Trend Demand Level 0.1 to 5.0 ^F HTRENDLV 0.1
Cool Trend Time 30 to 600 sec CTRENDTM 120
Heat Trend Time 30 to 600 sec HTRENDTM 120
DMDL
Demand Limit Select 0 to 3 DMD_CTRL 0
Demand Limit at 20 ma 0 to 100 % DMT20MA 100
Loadshed Group Number 0 to 99 SHED_NUM 0
Loadshed Demand Delta 0 to 60 % SHED_DEL 0
Maximum Loadshed Time 0 to 120 min SHED_TIM 60
Demand Limit Sw.1 Setpt. 0 to 100 % DLSWSP1 80
Demand Limit Sw.2 Setpt. 0 to 100 % DLSWSP2 50
ECON
Economizer Installed ? Yes/No ECON_ENA Yes
Econ. Act.2 Installed ? Yes/No ECON_TWO No
Economizer Min.Position 0 to 100 % ECONOMIN 5
Economizer Max.Position 0 to 100 % ECONOMAX 98
Economzr trim for sumZ ? Yes/No ECONTRIM Yes
Econ ChangeOver Select 0 to 3 ECON_SEL 0
OA Enthalpy ChgOvr Selct 1 to 5 OAEC_SEL 4
Outdr.Enth Compare Value 18 to 28 BTU/LBM OAEN_CFG 24
High OAT Lockout Temp 55 to 120 dF OAT_LOCK 60
OA Dewpoint Temp Limit 50 to 62 dF OADEWCFG 55
Outside Air RH Sensor Enable/Disable OARHSENS Disable
Outdoor Air CFM Sensor Enable/Dsable OCFMSENS Dsable
Economizer Min.Flow 0 to 20000 CFM OACFMMAX 2000
IAQ Demand Vent Min.Flow 0 to 20000 CFM OACFMMIN 0
Econ.Min.Flow Deadband 200 to 1000 CFM OACFM_DB 400
Economizer Prop.Gain 0.7 to 3.0 EC_PGAIN 1
Economizer Range Adjust 0.5 to 5 ^F EC_RANGE 2.5
Economizer Speed Adjust 0.1 to 10 EC_SPEED 0.75
Economizer Deadband 0.1 to 2 ^F EC_DBAND 0.5
Unoc Econ Free Cool Cfg 0-2 UEFC_CFG 0
Unoc Econ Free Cool Time 0-720 min UEFCTIME 120
Un.Ec.Free Cool OAT Lock 40-70 dF UEFCNTLO 50
Econ Serial Number 1 0-9999 ECON_SN1
Econ Serial Number 2 0-6 ECON_SN2
Econ Serial Number 3 0-9999 ECON_SN3
Econ Serial Number 4 0-254 ECON_SN4
Econ Ctrl Angle Lo Limit 0-90 ECONCALM 85
Econ 2 Serial Number 1 0-9999 ECN2_SN1
Econ 2 Serial Number 2 0-6 ECN2_SN2
Econ 2 Serial Number 3 0-9999 ECN2_SN3
Econ 2 Serial Number 4 0-254 ECN2_SN4
Ecn2 Ctrl Angle Lo Limit 0-90 ECN2CALM 85
EDTR
EDT Reset Configuration 0 to 3 EDRSTCFG 2
Reset Ratio 0 to 10 RTIO 3
Reset Limit 0 to 20 ^F LIMT 10
EDT 4-20 ma Reset Input Enable/Disable EDTRSENS Disable
HEAT
Heating Control Type 0 to 5 HEATTYPE 0
Heating Supply Air Setpt 80-120 dF SASPHEAT 85
Occupied Heating Enabled Yes/No HTOCCENA No
MBB Sensor Heat Relocate Yes/No HTLATMON No
Staged Heat Type 0 to 8 HTSTGTYP 0
Max Cap Change per Cycle 5 to 45 HTCAPMAX 45
St.Ht DB min.dF/PID Rate 0 to 5 HT_MR_DB 0.5
St.Heat Temp. Dead Band 0 to 5 ^F HT_SG_DB 2
APPENDIX B — CCN TABLES
Table O — SERVICE-CONFIG TABLES (cont)
TABLE DISPLAY NAME RANGE UNITS POINT NAME DEFAULT