202
HEAT (cont) Heat Rise dF/sec Clamp 0.05 to 0.2 HTSGRISE 0.06
LAT Limit Config 0 to 20 ^F HTLATLIM 10
Limit Switch Switch Monitoring? Yes/No HTLIMMON Yes
Limit Switch High Temp 110 to 180 dF HT_LIMHI 170
Limit Switch Low Temp 100 to 170 dF HT_LIMLO 160
Heat Control Prop. Gain 0 to 1.5 HT_PGAIN 1
Heat Control Derv. Gain 0 to 1.5 HT_DGAIN 1
Heat PID Rate Config 30 to 300 sec HTSGPIDR 90
Hydronic Ctl.Prop. Gain 0 to 1.5 HW_PGAIN 1
Hydronic Ctl.Integ. Gain 0 to 1.5 HW_IGAIN 1
Hydronic Ctl.Derv. Gain 0 to 1.5 HW_DGAIN 1
Hydronic PID Rate Config 15 to 300 sec HOTWPIDR 90
Hydronic Ht.Serial Num.1 0 to 9999 HTCL_SN1 0
Hydronic Ht.Serial Num.2 0 to 6 HTCL_SN2 0
Hydronic Ht.Serial Num.3 0 to 9999 HTCL_SN3 0
Hydronic Ht.Serial Num.4 0 to 254 HTCL_SN4 0
Hydr.Ht.Ctl.Ang.Lo Limit 0-90 HTCLCALM 85
HUMD
Humidifier Control Cfg. 0 to 4 HUMD_CFG 0
Humidifier Setpoint 0 to 100 % HUSP 40
Humidifier PID Run Rate 10 to 120 sec HUMDRATE 30
Humidifier Prop. Gain 0 to 5 HUMID_PG 1
Humidifier Integral Gain 0 to 5 HUMID_IG 0.3
Humidifier Deriv. Gain 0 to 5 HUMID_DG 0.3
Humd Serial Number 1 0 to 9999 HUMD_SN1 0
Humd Serial Number 2 0 to 6 HUMD_SN2 0
Humd Serial Number 3 0 to 9999 HUMD_SN3 0
Humd Serial Number 4 0 to 254 HUMD_SN4 0
Humd Ctrl Angle Lo Limit 0-90 HUMDCALM 85
IAQ_
Economizer Min.Position 0 to 100 % ECONOMIN 5
IAQ Demand Vent Min.Pos. 0 to 100 % IAQMINP 0
Economizer Min.Flow 0 to 20000 CFM OACFMMAX 2000
IAQ Demand Vent Min.Flow 0 to 20000 CFM OACFMMIN 0
Econ.Min.Flow Deadband 200 to 1000 CFM OACFM_DB 400
IAQ Analog Sensor Config 0 to 4 IAQANCFG 0
IAQ 4-20 ma Fan Config 0 to 2 IAQANFAN 0
IAQ Discrete Input Config 0 to 2 IAQINCFG 0
IAQ Disc.In. Fan Config 0 to 2 IAQINFAN 0
OAQ 4-20ma Sensor Config 0 to 2 OAQANCFG 0
IAQ Econo Override Pos. 0 to 100 % IAQOVPOS 100
IAQ Override flow 0 to 31000 CFM IAQOVCFM 10000
Diff.Air Quality LoLimit 0 to 1000 DAQ_LOW 100
Diff. Air Quality HiLimit 100 to 2000 DAQ_HIGH 700
DAQ PPM Fan Off Setpoint 0 to 2000 DAQFNOFF 200
DAQ PPM Fan On Setpoint 0 to 2000 DAQFNON 400
Diff. AQ Responsiveness -5 to 5 IAQREACT 0
OAQ Lockout Value 0 to 2000 OAQLOCK 0
User determined OAQ 0 to 5000 OAQ_USER 400
IAQ Low Reference 0 to 5000 IAQREFL 0
IAQ High Reference 0 to 5000 IAQREFH 2000
OAQ Low Reference 0 to 5000 OAQREFL 0
OAQ High Reference 0 to 5000 OAQREFH 2000
IAQ Purge Yes/No IAQPURGE No
IAQ Purge Duration 5-60 min IAQPTIME 15
IAQ Purge LoTemp Min Pos 0-100 % IAQPLTMP 10
IAQ Purge HiTemp Min Pos 0-100 % IAQPHTMP 35
IAQ Purge OAT Lockout 35-70 dF IAQPNTLO 50
APPENDIX B — CCN TABLES
Table O — SERVICE-CONFIG TABLES (cont)
TABLE DISPLAY NAME RANGE UNITS POINT NAME DEFAULT