CL-6
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -- - - - - - - - - - - - - - - - - - - -
CUT ALONG DOTTED LINE CUT ALONG DOTTED LINE
CONTROLS SET POINT AND CONFIGURATION LOG (cont)
ITEM EXPANSION RANGE DEFAULT SETTING
CCN CCN CONFIGURATION
CCNA CCN Address 1 to 239 1
CCNB CCN Bus Number 0 to 239 0
BAUD CCN Baud Rate 1 to 5 (multi-text strings) 3
BROD CCN BROADCST DEFINITIONS
BRODTM.DT CCN Time/Date Broadcast ON/OFF On
BRODOAT.B CCN OAT Broadcast ON/OFF Off
BRODORH.B CCN OARH Broadcast ON/OFF Off
BRODOAQ.B CCN OAQ Broadcast ON/OFF Off
BRODG.S.B Global Schedule Broadcst ON/OFF Off
BRODB.ACK CCN Broadcast Ack'er ON/OFF Off
SC.OV CCN SCHEDULES-OVERRIDES
SC.OVSCH.N Schedule Number 0 to 99 1
SC.OVHOL.T Accept Global Holidays? YES/NO No
SC.OVO.T.L. Override Time Limit 0 to 4 HRS 1
SC.OVOV.EX Timed Override Hours 0 to 4 HRS 0
SC.OVSPT.O SPT Override Enabled ? YES/NO Yes
SC.OVT58.O T58 Override Enabled ? YES/NO Yes
SC.OVGL.OV Global Sched. Override ? YES/NO No
ALLM ALERT LIMIT CONFIG.
SP.L.O SPT lo alert limit/occ -10 to 245 dF 60
SP.H.O SPT hi alert limit/occ -10 to 245 dF 85
SP.L.U SPT lo alert limit/unocc -10 to 245 dF 45
SP.H.U SPT hi alert limit/unocc -10 to 245 dF 100
SA.L.O EDT lo alert limit/occ -40 to 245 dF 40
SA.H.O EDT hi alert limit/occ -40 to 245 dF 100
SA.L.U EDT lo alert limit/unocc -40 to 245 dF 40
SA.H.U EDT hi alert limit/unocc -40 to 245 dF 100
RA.L.O RAT lo alert limit/occ -40 to 245 dF 60
RA.H.O RAT hi alert limit/occ -40 to 245 dF 90
RA.L.U RAT lo alert limit/unocc -40 to 245 dF 40
RA.H.U RAT hi alert limit/unocc -40 to 245 dF 100
OAT.L OAT lo alert limit -40 to 245 dF -40
OAT.H OAT hi alert limit -40 to 245 dF 150
R.RH.L RARH low alert limit 0 to 100% 0
R.RH.H RARH high alert limit 0 to 100% 100
O.RH.L OARH low alert limit 0 to 100% 0
O.RH.H OARH high alert limit 0 to 100% 100
SP.L SP low alert limit 0 to 5 " H2O 0
SP.H SP high alert limit 0 to 5 " H2O 2
BP.L BP lo alert limit -0.25 to 0.25 " H2O -0.25
BP.H BP high alert limit -0.25 to 0.25 " H2O 0.25
IAQ.H IAQ high alert limit 0 to 5000 1200
TRIM SENSOR TRIM CONFIG.
SAT.T Air Temp Lvg SF Trim -10 to 10 ^F 0
RAT.T RAT Trim -10 to 10 ^F 0
OAT.T OAT Trim -10 to 10 ^F 0
SPT.T SPT Trim -10 to 10 ^F 0
L.SW.T Limit Switch Trim -10 to 10 ^F 0
CCT.T Air Temp Lvg Evap Trim -10 to 10 ^F 0
DTA.1 A1 Discharge Temp Trim -10 to 10 ^F 0
SP.A.T Suct.Press.Circ.A Trim -50 to 50 PSIG 0
SP.B.T Suct.Press.Circ.B Trim -50 to 50 PSIG 0
DP.A.T Dis.Press.Circ.A Trim -50 to 50 PSIG 0
DP.B.T Dis.Press.Circ.B Trim -50 to 50 PSIG 0