CL-7
CONTROLS SET POINT AND CONFIGURATION LOG (cont)
*Model number dependent.
ITEM EXPANSION RANGE DEFAULT SETTING
SW.LG SWITCH LOGIC: NO / NC
FTS.L Filter Status Inpt-Clean Open/Close Open
IGC.L IGC Feedback - Off Open/Close Open
RMI.L RemSw Off-Unoc-Strt-NoOv Open/Close Open
ENT.L Enthalpy Input - Low Open/Close Close
SFS.L Fan Status Sw. - Off Open/Close Open
DL1.L Dmd.Lmt.Sw.1 - Off Open/Close Open
DL2.L Dmd.Lmt.Sw.2 - Off Open/Close Open
IAQ.L IAQ Disc.Input - Low Open/Close Open
FSD.L Fire Shutdown - Off Open/Close Open
PRS.L Pressurization Sw. - Off Open/Close Open
EVC.L Evacuation Sw. - Off Open/Close Open
PRG.L Smoke Purge Sw. - Off Open/Close Open
DH.LG Dehumidify Sw. - Off Open/Close Open
DISP DISPLAY CONFIGURATION
TEST Test Display LEDs ON/OFF Off
METR Metric Display ON/OFF Off
LANG Language Selection 0 to 1 (multi-text strings) 0
PAS.E Password Enable ENABLE/DISABLE Enable
PASS Service Password 0000 to 9999 1111
S.VFD SUPPLY FAN VFD CONFIG
N.VLT VFD1 Nominal Motor Volts 0 to 999 VOLTS 460*
N.AMP VFD1 Nominal Motor Amps 0 to 999 AMPS 55.0*
N.FRQ VFD1 Nominal Motor Freq 10 to 500 60
N.RPM VFD1 Nominal Motor RPM 50 to 30000 1750
N.PWR VFD1 Nominal Motor HPwr 0 to 500 40*
M.DIR VFD1 Motor Direction 0 to 1 (multi-text strings) 0
ACCL VFD1 Acceleration Time 0 to 1800 sec 30
DECL VFD1 Deceleration Time 0 to 1800 sec 30
SW.FQ VFD1 Switching Frequency 0 to 3 (multi-text strings) 2
TYPE VFD1 Type 0 to 1 (multi-text strings) 0
E.VFD EXHAUST FAN VFD CONFIG
N.VLT VFD2 Nominal Motor Volts 0 to 999 VOLTS 460*
N.AMP VFD2 Nominal Motor Amps 0 to 999 AMPS 28.7*
N.FRQ VFD2 Nominal Motor Freq 10 to 500 60
N.RPM VFD2 Nominal Motor RPM 50 to 30000 1750
N.PWR VFD2 Nominal Motor HPwr 0 to 500 20*
M.DIR VFD2 Motor Direction 0 to 1 (multi-text strings) 0
ACCL VFD2 Acceleration Time 0 to 1800 sec 30
DECL VFD2 Deceleration Time 0 to 1800 sec 30
SW.FQ VFD2 Switching Frequency 0 to 3 (multi-text strings) 2
TYPE VFD2 Type 0 to 1 (multi-text strings) 0