CaterSense the Intelligent answer
CS-INST1-0.01
Model: CaterSense 01 Page 11 07-11
2.045 - FAN OVERCURRENT
Cause:- The indicated fan is drawing more current than the maximum current
established during commissioning.
Solution:- Ensure fan is working correctly. Check running current with an
ammeter. Check filters are clean. Use the diagnosis mode to
establish any problems with set-up. The system must be reset by
pressing "STOP" before it can be restarted.
2.048 - EMERGENCY STOP
Cause:- The system has been manually stopped by pressing SYSTEM STOP
Solution:- Reset the system by pressing SYSTEM STOP a second time.
If the above does not solve your problem, contact Trent Products.