2.04 Troubleshooting
2.041 - SYSTEM STOPPED
Cause: - The system has been stopped
Solution: - Press "Start" key to begin startup sequence
2.042 - FIRE ALARM
Cause: - The link between terminals 9 and 10 has been broken (fire alarm
activated).The fan and gas valve outputs will be deactivated.
Solution: - Ensure fire alarm is not activated. Check wiring to fire alarm interface panel.
The system must be reset by pressing "STOP" before it can be restarted.
2.043 - KNOCK OFF BUTTON
Cause:- The link between terminals 11 and 12 has been broken (knock off
pressed). The gas valve output will be deactivated.
Solution:- Ensure remote knock off button has been released. Check wiring to remote
knock-off button. The system must be reset by pressing "STOP" b
before it can be restarted.
2.044 - FAN UNDERCURRENT
Cause:- The indicated fan is drawing less current than the minimum current
established during commissioning.
Solution:- Ensure fan is working correctly. Check running current with an
ammeter. Use the diagnosis mode to establish any problems with set-up.
The system must be reset by pressing "STOP" before it can be restarted.