EasyManuals Logo

CaterSense -01 User Manual

Default Icon
12 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #10 background imageLoading...
Page #10 background image
CaterSense the Intelligent answer
CS-INST1-0.01
Model: CaterSense 01 Page 10 07-11
2.04 Troubleshooting
2.041 - SYSTEM STOPPED
Cause: - The system has been stopped
Solution: - Press "Start" key to begin startup sequence
2.042 - FIRE ALARM
Cause: - The link between terminals 9 and 10 has been broken (fire alarm
activated).The fan and gas valve outputs will be deactivated.
Solution: - Ensure fire alarm is not activated. Check wiring to fire alarm interface panel.
The system must be reset by pressing "STOP" before it can be restarted.
2.043 - KNOCK OFF BUTTON
Cause:- The link between terminals 11 and 12 has been broken (knock off
pressed). The gas valve output will be deactivated.
Solution:- Ensure remote knock off button has been released. Check wiring to remote
knock-off button. The system must be reset by pressing "STOP" b
before it can be restarted.
2.044 - FAN UNDERCURRENT
Cause:- The indicated fan is drawing less current than the minimum current
established during commissioning.
Solution:- Ensure fan is working correctly. Check running current with an
ammeter. Use the diagnosis mode to establish any problems with set-up.
The system must be reset by pressing "STOP" before it can be restarted.
POWER ON GAS VALVE
SYSTEM CONDITION
REMOTE KNOCK OFF FAN1
FIRE ALARM FAN2
POWER ON GAS VALVE
SYSTEM CONDITION
REMOTE KNOCK OFF FAN1
FIRE ALARM FAN2
POWER ON GAS VALVE
SYSTEM CONDITION
REMOTE KNOCK OFF FAN1
FIRE ALARM FAN2
POWER ON GAS VALVE
SYSTEM CONDITION
REMOTE KNOCK OFF FAN1
FIRE ALARM FAN2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the CaterSense -01 and is the answer not in the manual?

CaterSense -01 Specifications

General IconGeneral
BrandCaterSense
Model-01
CategoryController
LanguageEnglish