Specifies minimum distance from wall for ceiling mounting.
Details minimum distance from peak for cathedral or peak ceilings.
Defines minimum and maximum distances from the ceiling for wall mounting.
Explains how to designate a master alarm and its LED indication.
Describes how alarms confirm interconnection via LED flashing.
Mark screw holes on the ceiling using the mounting base ring.
Use screws/plugs for installation and click alarm into base.
Trace cover ring, then cut hole using a hole saw (81-85mm).
Insert, secure base, activate alarm, and place cover ring.
Press test button for 6.5s to send a test signal to connected alarms.
Single beep (connected), three beeps (fault).
Short press stops beeps; visit website for troubleshooting.
Photoelectric alarm with 85 dB sound level at 3 metres.
Powered by two non-replaceable 3v CR123A, 1600mAh lithium batteries.
| Type | Photoelectric Smoke Alarm |
|---|---|
| Power Source | Battery |
| Battery Life | 10 years |
| Alarm Sound | 85 dB at 3 meters |
| Battery | 3V Lithium Battery |
| Operating Temperature | 0°C to +55°C |
| Standards | EN 14604 |