Maintenance and care -
Joint Cutter CF-22 E.800
Table 1 A: Recurrent tests of stationary electrical installations and equipment
System/equipment Test period Type of test Inspector
Electric systems and stationary
equipment
4years for proper condition electrician
Electrical equipment and stationary
electric equipment in "special
installations or locations"
(DIN VDE 0100 group 700)
1year
Portable residual current devices 1month for eciency Electrician or person trained
in electric equipment using
suitable measurement and
testing equipment
Circuit breakers, dierential current
and fault voltage safety switches
– in stationary equipment
– in mobile equipment
6months
every work day
for correct operation by
actuating the testing facility
User
5.6 Security check of the electric equipment acc. to BGV A3 §5, implementing regulations
paragraph 1 No. 2
Table 1 B: Recurrent tests of non-stationary electrical equipment
System/equipment Test period standard and
maximum values
Type of test Inspector
– mobile electric equipment
(ifused)
– extension and device
connection cords with plugs
– connecting lines with plugs
– movable lines with plugs and
xed connection
Standard value 6 months,
on construction sites 3 months.
If the tests yield a fault rate < 2%,
the test period can be extended
accordingly.
Maximum values:
at construction sites, in
production sites and shops or
under similar conditions one year,
in oces and under similar
conditions two years.
for proper
condition
Electrician or person trained
in electric equipment using
suitable measurement and
testing equipment
For more information see BG information "Selection and operation of electric equipment on construction sites and at assembly locations" (BGI 608)