EasyManua.ls Logo

Certikin COH180 - Page 50

Default Icon
96 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4
(NOTE: The Heater is delivered set to display in
Fahrenheit. For a Centigrade display, see 7:3
Commissioning Section of Installation Instructions)
Pool Temperature Mechanical Stop
Stop
This can be used to obtain a repeatable
setting and to limit maximum pool temperature. To
set, loosen the screw, adjust as required and then
re-tighten.
Pool Temperature Display
Display
- Normally shows the actual Pool Tem-
perature, but also displays the Setting Temperature
and a Setting Dot lit whilst being adjusted. The
display is also used for commissioning and diag-
nostic purposes.
Heating Demand LED - GREEN
(Only in use when heating system connected)
Off
- There is no Heating Demand , heating is
switched off.
On
- There is a Heating Demand , heating is on but
not yet up to temperature.
Flashing
- The Heating Demand is Met , heating is
up to temperature.
Heating Temperature Control Knob
(
Only used when heating system connected)
Off
- There is no Heating Demand, heating is
switched off.
Normal
- Normal setting for heating, it can be
adjusted lower if required.
(NOTE: Supplied set for Pool Priority. It will satisfy
the Pool Temperature before supplying full Heating.
To change the priority, see 7:3 Commissioning
Section of the Installation Instructions)
Filter LED - YELLOW
On -
Pool Filter Blocked - Insufficient pressure,
possibly due to a blocked pool filter. The heater will
not run.
Flashing
- Clean Pool Filter - The filter may require
back washing. The heater will run. Can be reset by
turning the Pool Temperature knob off and back on
again.
Lockout - Oil? LED - RED
On -
Lockout - Oil? - This indicates that the burner
cannot fire, the probable cause is lack of fuel oil.
Check the oil tank. After 3 minutes press the
Button on the front of the Burner to reset. If the
problem persists consult your Service Engineer.
Boiler Overheat LED - RED
On
- Boiler Overheat - This indicates that the
Heater has overheated and shut down. See Press
to Reset Button instructions below.
Press to Reset Button
Press
- Press Reset Button when boiler has
cooled down. If the problem persists consult your
Service Engineer.
Automatic Frost Protection
The Heater will automatically run a Frost Protec-
tion routine if the temperature falls below 3°C
(37°F). The Pool Temperature Display will show
0°C. This will include the use of the Pool Pump if
connected to the Heater.
1:7 Re-Pressurising
Connect a Mains Water supply then connect the
free end of the braided flexible hose (the Filling
Loop) (see Fig.2:1b) to the incoming mains con-
nector.
Open the Valve to the supply, then, slowly open the
Valve on the Side Panel until the Pressure Gauge
shows 1 Bar.
Close both valves then disconnect the Filling Loop.
1:8 Running the Pool Pump
If this option has been installed the Heater can run
the Pool Pump on its own. Turn the Pool Tempera-
ture Control Knob to ‘Pump’, just next to Off.
9-04-02

Other manuals for Certikin COH180

Related product manuals