Questions and Answers

  • H
    Haley FlowersSep 23, 2025
    What to do if my CG DC Drives show Err41?
    • R
      Richard DunnSep 23, 2025
      If your CG DC Drive displays Err41, and E0.18 = 00100, it means that the current output amp is more than E0.19. Check the current load.
  • M
    Michael AdamsAug 25, 2025
    What to do if my CG Emotron VS show Err29?
    • T
      turnerpatrickAug 25, 2025
      If your CG DC Drive displays Err29, it indicates a fault that can arise from several causes. Here's what you should check: 1. The inverter output circuit is grounded or short-circuited: Troubleshoot peripheral problems. 2. The acceleration and deceleration time is too short: Increase the acceleration time. 3. Manual torque boost or V/F curve is not appropriate: Adjust the manually torque boost or V/F curve. 4. Voltage too low: Adjust the voltage to normal range. 5. Starting the running motor: Select RPM track start or start after the motor has stopped. 6. Sudden load in the acceleration process: Cancel the sudden load. 7. Model selection of inverter power is too small: Select an inverter with a higher rating.
  • D
    Dillon CastroAug 25, 2025
    What to do if my CG Emotron VS show Err02?
    • T
      Thomas GarciaAug 26, 2025
      If your CG DC Drives display Err02, it could be due to: * The output circuit being grounded or short-circuited: Eliminate external faults. * The deceleration time is too short: Increase the deceleration time. * The voltage is too low: Adjust the voltage to normal range. * A sudden load is added during deceleration: Remove the added load. * The braking unit and braking resistor are not installed: Install the braking unit and braking resistor.
  • K
    Kelly KingAug 26, 2025
    What to do if my CG Emotron VS show Err30?
    • B
      Bruce RoseAug 27, 2025
      If your CG DC Drive shows Err30, consider the following potential causes and solutions: 1. Input voltage is too high: Adjust the voltage to the normal range. 2. There is external force dragging the motor to run in the deceleration process: Cancel external force or install a brake resistor. 3. The deceleration time is too short: Increase the deceleration time. 4. No installation of braking resistor: Install braking resistor.
  • J
    Jose FlowersAug 27, 2025
    What to do if my CG Emotron VS DC Drives show Err03?
    • A
      ashleymedinaAug 27, 2025
      If your CG DC Drives display Err03, it may be caused by: * The output circuit being grounded or short-circuited: Eliminate external faults. * The voltage is too low: Adjust the voltage to normal range. * A sudden load is added during operation: Remove the added load. * The AC drive model is of too small power class: Select an AC drive of higher power class.
  • P
    Patrick WardSep 13, 2025
    What to do if my CG Emotron VS DC Drives show Err13?
    • L
      Larry ZimmermanSep 13, 2025
      If your CG DC Drives display Err13, it indicates that an external fault signal is input via DI. Reset the operation.
  • G
    gmartinezSep 12, 2025
    What to do if my CG Emotron VS DC Drives show Err23?
    • P
      pwilliamsSep 12, 2025
      If your CG DC Drives are showing Err23, it could be because: * The brake line failure or damage the brake pipe: Check the brake unit, replace the brake pipe. * An external braking resistor is too small: Increase the braking resistor.
  • S
    Shannon WilsonSep 12, 2025
    What to do if my CG Emotron VS show Err18?
    • V
      Vicki BrownSep 12, 2025
      If your CG DC Drives display Err18, it could be due to: * The PC is not working properly: Check the PC Connection. * The communication line is not normal: Check the communication cable. * H0 set communication parameters set incorrectly: The communication parameters are set correctly.
  • J
    Jason PowellSep 4, 2025
    What to do if my CG Emotron VS show Err39?
    • G
      Gordon FisherSep 4, 2025
      If your CG DC Drive displays Err39, consider these possible causes: 1. PTC sensor configuration not right: Reset PTC sensor parameter. 2. Motor temperature protection value too small: Increase motor temperature protection value. 3. Motor temperature too high: Wait until the motor is cooled.
  • K
    Kenneth CohenSep 2, 2025
    What to do if my CG Emotron VS show Err14?
    • C
      Cheryl FoxSep 2, 2025
      If your CG DC Drives display Err14, it might be due to: * The ambient temperature is too high: Lower the ambient temperature. * The air filter is blocked: Clean the air filter. * The fan is damaged: Replace the damaged fan. * The thermally sensitive resistor of the module is damaged: Replace the damaged thermally sensitive resistor. * The inverter module is damaged: Replace the inverter module.

CG Emotron VS Series Specifications

General IconGeneral
SeriesVS Series
TypeDC Drives
Supply Voltage380-690 V AC
Field SupplyIntegrated field supply
Input Voltage380 - 690 V AC
Control MethodMicroprocessor control
Cooling MethodForced air cooling
Protection FeaturesOvercurrent, overvoltage, undervoltage, overtemperature, field loss, short circuit, earth fault
Communication InterfacesRS485, Ethernet (optional)

Related product manuals