5,Malfunction codeF6 the outdoor temp sensor fault
6,Malfunction code FA the communication fault between the wire controller to the indoor PCB
Turn off the power
Take out the temperature sensor from outdoor PCB. Then test
this outdoor temperature sensor resistance whether ii is normal
(the normal: discharge sensor is 3K~200K the other sensor is
1K~40K).
N
The outdoor temp sensor is
bad, Please change it.
Y
Connect the sensor with the indoor PCB again.
Check the sensor and the indoor PCB terminal
resistance. The normal value is 0Ω
N
The indoor temperature sensor adapter
connector is loose. Change this indoor
PCB or repair this adapter connector
Y
The indoor PCB is bad. Please change it
Electrify and turn on the unit
Check the connecting linewire controller
PCB whether they are loose or have a bad
contact.
Y
Please change the connecting line or
repair the loose terminal
N
Faulty cause1maybe the indoor coil
temp sensor’s BNC connector plugs is
loose or contact ill;
2the sensor is bad or the down-lead is
circuit-breakcircuitshort
3the indoor PCB’s hardware has been
damaged
The faulty cause
1the wire controllers connecting plug
is loose or contacts ill
2the wire controller’s hardware has
been damaged ;
3the indoor PCB has been damaged.