7,Malfunction code
P2 the outdoor unit transducer module protection faulty
Turn off the power
1whether the compressors connecting wiring is
loose
2check whether the module and radiator are
firm
N
1please make the compressors
connecting wiring firm
2please fixup the IPM and radiator
together
The dynatron Q3 reference value:
be pole :The positive pole resistance660Ω the negative
pole resistance961Ω;
bc pole :The positive pole resistance659Ω the negative
pole resistance :1439Ω
The clamping diode’s parameter:
VD15 The positive pole resistance389Ωthe negative pole resistance
392Ω
VD16 The positive pole resistance497Ωthe negative pole resistance
1012Ω
The faulty cause
1 the compressors connecting
wiring is loose;
2the IPM module and radiator are
not firm
3the IPM board has the fault.
4PFC board hardware issue
5the com
p
ressor is bad.