8 The malfunction code:
P3 (The indoor input current is large)
Y
Check whether the compressor’s winding
value is normal refer to SNYO
C-6RZ146H1A winding value: T-R 0.452Ω
T-S0.452Ω R-S0.452Ω)
N
The compressor is badthen
change it.
Change IPM board, check
whether it is normal
Y
Turn on the unit
Check the ambient temperature whether it is more
than the running temperature(cooling:10~46,
hot:-15~24)
Y
Please wait the conditions returned to
normal then run it if the operating
conditions is very bad.
The faulty cause
1the ambient temp exceed the temp
range of the A/C’s running
2the outdoor PCB’s hardware is bad
3, disconnecting valve of outdoor is
close.
4
,
outdoo
r
motor can’t run.
Change PFC board
N
Y
The IPM board is bad, change it.
Outdoor motor can’t run. Check whether the
winding of motor is normal or not. ( main
windings is about 100Ω, the aux winding is
about 200Ω)
Check whether shutoff valve of outdoor is
open.
Open the shutoff valve
Motor damages. Change motor.
Y
Y
N
N