The faulty cause:
1, the compressor crustal temp switch has been damaged
2, outdoor ambient temp go beyond the limited
3, compressor discharge temp is overhigh
4, module tem
ond the limited
Annotation 1:The normal value of the phase current:18K<11A;24K<13A;28K<15A
9, The malfunction code:P4 (compressor discharge temp is overhigh、outdoor ambient temp go beyond the
limited、compressor crustal temp switch is disconnected、module temp go beyond the limited)
N
Check the connection position between motor and
outdoor PCB whether is loose ,
(Please insert and pull out the terminal over and
over, check whether the motor is normal)
N
The refrigerant is more than
usual. Please let it out.
The outdoor PCB is bad.
Please change it
Y
Whether the pressure
is normal? (the normal
value : the high is
2.4~3.06MPa. the low
is 1.2~1.6MPa
N
Check the
compressor phase
current whether it
is large. Please
change it if the
value is large.
Y
Turn off the power
Check whether the compressor crustal temp
switch is disconnected.
Y
Compressor crustal temp switch
has been damaged,then change
it。
N
Check whether the outdoor ambient temp is
overhigh or overlow.
Y
The fault will disappear when
the outdoor ambient temp is
beyond minus 20℃ and under
plus 55℃.
N
Please Charge the refrigerant.
N
Check whether the A/C units’ pressure is normal
(the normal value:high pressure 3.06Mpa low
pressure 1.6Mpa)when the A/C unit operate
Check whether the current is normal?
the normal current:18K< 13A. 24K,
<15A. 28K<17A
Change motherboard of outdoor
PCB if still can’t run after using that
method.
Y
N