Chigo CS-25V1A-H1; CS-35V1A-E2; CS-50V9A-S; CS-70V9A-T - 10, The malfunction code: P7 (The outdoor unit DC generatrix voltage is abnormal)

Chigo CS-25V1A-H1; CS-35V1A-E2; CS-50V9A-S; CS-70V9A-T
66 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
10The malfunction code:
P7 The outdoor unit DC generatrix voltage is abnormal
Y
1check whether module temp sensorresistance is
normal (the normal value range:140KΩ)
2 check whether the module and radiator are firm
3 check whether the disperse heat silica gel is short
or dry
4 check whether the module has been damaged.
N
1Change the temp sensor
2 Firm the module and
radiator
3Append anew the disperse
heat silica gel
4Change the module
Y
Please change the outdoor PCB
Turn off the supply
Check whether the power voltage is in the
normal voltage range “150V270V”
N
Ensure the power voltage is in the
normal voltage range“150V270V
Y
The IPM basic board hardware has been damaged
please change the IPM basic board
The faulty cause
1, The power voltage is
abnormal
2, The IPM basic board
hardware has been damaged