The faulty cause
1、 the high and low pressure valve are
closed
2、 the refrigerant leaks from the A/C
system
3、 the indoor and outdoor pipe temp
sensor are loose or hang in the air.
4、 the indoor and outdoor pipe temp
sensor has been dama
ed.
11、The malfunction code:
P8 (lack the refrigerant or reverse valve fault)
Turn off the power
Check whether the high and low pressure valves are open
N
Open the high and low pressure
valve
Check whether the system pressure is normal (the
normal value : high pressure3.06Mpa low
pressure1.6Mpa)
N
Due to refrigerant leakage,kook for the
leak to weld it,then charge anew the
refrigerant to the system.Fig.9~17
Please change it if the sensor wire is
short circuit or open circuit.
N
Y
Check whether the indoor and outdoor pipe
temp sensor are loose or hang in the air.
Y
Please arrange the indoor and outdoor
sensor correctly and change it if the probe
spring piece is damaged.
Y
Fig. 15、 please make sure that
there is enough soap bubble.