17
P42 = Operative set point alignment at
instrument start up
0 = At start up, the operative set point will be
aligned to SP or SP2 according to the digital
input status.
1 = At start up, the operative set point will be
aligned to the measured value, the selected
set point value will be reached by the
programmed ramp (see Grd1 and Grd2
operative parameters).
NOTE: if the instrument detects an out of range
or an error condition on the measured value it will
ever operate as described for P42 = 0.
The configuration procedure is terminated and the
display returns to show "COnF".
1604-1-BC.p65 5/16/00, 10:25 AM17