86 Chromalox 2104 Technical Manual
Sensor Leadwire Effect
J Thermocouple +1°F for 1000 Ft. of 18 AWG extension wire
K Thermocouple +5°F for 1000 Ft. of 18 AWG extension wire
E Thermocouple +4°F for 1000 Ft. of 18 AWG extension wire
R Thermocouple +3°F for 1000 Ft. of 18 AWG extension wire
S Thermocouple +3°F for 1000 Ft. of 18 AWG extension wire
B Thermocouple +6°F for 1000 Ft. of 18 AWG extension wire
T Thermocouple +1°F (temperatures > -80°C)
+2°F (temperatures < -80°C)
RTD, 4-20mA, 1-5 Vdc ±0.1% of Sensor Span/20Ω balanced leadwire resistance