94 Chromalox 2104 Technical Manual
Control Page (continued)
Menu Description Available Settings Factory Settings Security
CC
CC
C
ONTONT
ONTONT
ONT Controller Type HEAT = Reverse Acting HEAT C
Output Controller
COOL = Direct Acting Single
Output Controller
HTCL = Heat/Cool Controller
CC
CC
C
OOOO
OOOO
OO
LL
LL
L Cooling PID2 = Uses PID2 settings PID2
Medium for cooling
AIR = Air Cooling
OIL = Oil Cooling
H2O = Water Cooling
RSPRSP
RSPRSP
RSP Remote OFF OFF
Setpoint ON
Enable
ENTIENTI
ENTIENTI
ENTI Event/Digital NONE = Disabled NONE
Function PID2 = PID2 enable
AUSP = Auxiliary SP enable
RSP = Remote SP enable
OUTD = Output disable
RS = Ramp/Soak
AUTO = Auto/Manual
AIR = Alarm Reset
AA
AA
A
UU
UU
U Auxiliary NONE = Disabled NONE
Pushbutton PID2 = PID2 enable
Function AUSP = Auxiliary SP enable
RSP = Remote SP enable
OUTD = Output disable
AUTO = Auto/Manual
AA
AA
A
OUTOUT
OUTOUT
OUT Analog NONE = Disabled ASP
Output PROC = Process Variable
Assignment ASP = Active Setpoint
OUT1 = Control Output !
OUT2 = Control Output 2
RSENRSEN
RSENRSEN
RSEN Ramp/Soak OFF OFF
ON
CC
CC
C
ODEODE
ODEODE
ODE User Selected 0-122 = Level A 0 D
Security Code 123-457 = Level B
458-735 = Level C
736-999 = Level D
See pages 35-37 for details.
Control Page