1.2.- î WARNINGS!
THE CURRENT USED FOR MEASUREMENTS, 20 A with the MPC-
20 and 50 A in the MPC-50, IS SUFFICIENT TO CREATE SIGNIFICANT
VOLTAGES AROUND THE ELECTRODES, ESPECIALLY THE AUXILIARY
ELECTRODES.
PLEASE TAKE ALL NECESSARY PRECAUTIONS TO AVOID
ACCIDENTS.
For example: A 5 Ohms auxiliary electrode creates a voltage of 250 V around
itself.
VOLTAGE MAY REACH 600 V AROUND THE CABLE OUTPUT with the
MPC-20 and 400 V with the MPC-50.
THE POWER CIRCUIT CONNECTIONS MUST NEVER BE
HANDLED WITHOUT HAVING FIRST STOPPED THE EQUIPMENT AND
REMOVED THE OPERATING KEY.
BEFORE ANY MEASUREMENTS ARE TAKEN, SIGNS MUST
PREVENT PEOPLE FROM PASSING THROUGH OR REMAINING IN THE
INJECTED CURRENT AREA. IN THE EVENT OF HIGH GROUND
RESISTANCES, VOLTAGES UP TO 600 V MAY BE CREATED, WHICH ARE
FATAL TO ANIMALS OR PERSONS NEAR TO THE DISPERSERS DURING
TESTS.