EasyManua.ls Logo

Circutor RGU-10A - WGC TRANSFORMERS

Circutor RGU-10A
52 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
11
Instruction Manual
RGU-10A, RGU-100A
3.4.2. RGU100A
A2
A1
1
2
3
4
5
6
7
8
19
20
22
23
24
Figure 5: Terminals of the RGU-100A: Upper - Lower.
Table 5: List of RGU-100A terminals.
Device terminals
A1: A1, Power supply 7: 1S1, Transformer connection WGC
A2: A2, Power supply 8: 1S2, Transformer connection WGC
1: R1, Trip relay (NO) 19: TRIP/RESET, Input for trigger or external reset
2: R1, Trip relay (NC) 20: TRIP/RESET, Input for trigger or external eset
3: C1, Trip relay (Common) 22: S, GND for RS-485
4: R2, Pre-alarm relay (NO) 23: B-, RS-485
5: R2, Pre-alarm relay (NC) 24: A+, RS-485
6: C2, Pre-alarm relay (Common)
3.5 - WGC TRANSFORMERS
The transformer is designed for wall-mounting or DIN-rail assembly with an accessory for installation.
The WGC is a feed-thru busbar type transformer, where the conductor cables to be measured must
pass through the inner hole or window of the transformer.
3.5.1 PANEL INSTALLATION
For panel installation, 4 clamping clips are provided with the transformer, see Figure 6.
Figure 6: Clamping clip.
The clamping clips must be installed on the WGC, as shown in Figure 7.

Table of Contents

Related product manuals