Instruction Manual
RGU-10A, RGU-100A
8.3.3.3.- Trip Relay Configuration
Table 27: Modbus Memory Map: Trip Relay Configuration.
Trip Relay Configuration
Configuration
parameter
Format Address Valid data range
Default
value
Trip Relay Polarity Unit [16] 37DC
0: standard polarity
1: positive polarity
0
Trip current limit Unit [16] 377D
0: 30 A
1: 3 A
0
Enable remote trip Unit [16] 377E
0: Disabled
1: Enabled
0
8.3.3.4.- RS-485 communications
Table 28: Modbus Memory Map: RS-485 Communications.
RS-485 Communications
Configuration
parameter
Format Address Valid data range Default value
Peripheral number Unit [16] 36B0 1 ... 247 1
Baud rate Unit [32] 36B1 - 36B2
4800, 9600, 19200, 38400,
57600, 115200
115200
Data format Unit [16] 36B3
0: 8N1, 1: 8E1, 2: 801
3: 8N2, 4: 8E2, 5: 802
0