FL-20A Instruction Manual - Page 31
Model FL-20A Cable Fault Locator
Recommendations
15. Record the actual voltage where a cable fails during hipot test-
ing. Halt the test immediately after failure.
16. When hipot testing cables, do not allow the hipot tester to keep
burning a fault once it is detected. This will reduce accuracy in
fault location with the FL-20A.
17. When using the FL-20A on cables that failed hipot testing above
15.00 kVDC or 10.5 kVAC, regard the results as suspect unless
the FL-20A reports “Standard” or “Exceptional” results.