&MGPEVDU.5
16.14 List of the parameters accessible by the thermostat
Par Description range UM Def.
P01
BandaLavoro:
Working band
0 ÷ 15.0 °C 2.0
P02
MaxH2Ocool:
Water max. temperature for cooling operating
0 ÷ 30.0 °C 20.0
P03
MinH2OHeat:
Water min. temperature for heating operating
0 ÷ 40.0 °C 30.0
P05
TimeOnPeriodical
Denes the duration of the OFF phase of the periodical
0 ÷ 999 min 2
P06 TempoOPeriodica 0 ÷ 999 min 5
Denes the duration of the OFF phase of the periodical
P10 OsetEco 0 ÷ 4.0 °C 3.0
P11
SetUrHeat:
Heat UR set point
30 ÷ 70 % 50
P12
BandUrHeat:
Intervention band of the heat humidier
0 ÷ 10 % 5
P21
FanOCool:
Fan status at “cooling” thermoregulator, satised
0: stop, 1: continuous, 2: periodical
0…2 num. 2
P22
FanOHeat:
Fan status at “heating” thermoregulator, satised
0: stop, 1: continuous, 2: periodical
0...2 num 0
P31
ModoAuto:
It enables the automatic saison change
0: Manual, 1: Auto
0…1 ag 0
P41 BT1 probe calibration -9.9+10.0 °C 0.0
P42 BT2 probe calibration -9.9+10.0 °C 0.0
P43 Thermostat temp. probe calibration -9.9+10.0 °C 0.0
P44 Thermostat UR probe calibration -9.9+10.0 %UR
S01 TESToperativa °C
S02 TH2Ooperativa °C
S03 TARIAoperativa °C
S04 URoperativa Hr%
S05 ActualMode bitmap
S06 CurrentSetpoint °C
S07 Current humidity Set Hr%
S08 Errors bitmap
S09 Active humidifcation ag
S10 Active dehumidication ag
S11
FanStatus:
0: o, 1: on
0…1 ag
S12
Actual fan:
0-7 if motor 0-10 V
0-3 if 3 speed motor
0-1 if single-speed motor
0…7 num.