220-240V
50Hz
1275×880×420
1275×994×420
1360×1284×420
1390×1244×540
1390×1424×540
1390×1670×540
1830×1520×770
1900×1720×845
53.6
59
71.5
74.4
80
90
181.5
208.5
100
90
100
140
160
180
200
200
300
400
500
800
1000
1500
2000
81.1
75.5
77.7
80.6
78.7
82.8
75.5
77.2
77.5
72.1
73.5
74.0
72.3
76.0
69.4
74.7
45
48
48
50
55
54
69
70
0.07
0.10
0.32
0.38
0.68
0.95
0.15
0.64
0.84
0.97
2.4
2.9
3.8
5.7
1.2
Φ144
Φ144
Φ198
Φ244
Φ244
Φ244
346×326
346×326
5.1 Specification Parameter
90
0.11
5. SPECIFICATION PARAMETER
Table 5-1
Table 5-2
Model
Power
supply
Packing
size(mm)
Air outlet
dimension
(mm)
Net
weight (kg)
Static
pressure
(Pa)
Nominal air flow
(m
3
/h)
Model
Power input(kW)
Current(A)
Nominal temp.
efficiency
Nominal enthalpy
efficiency
10
Notes
There are 3 steps of fan speed (High, Medium, Low), all the parameters
in the above table is measured at the high speed.
Communication wiring between the indoor and outdoor units
The HRV and outdoor units communicate via the RS485 serial port.
The communication wiring between the HRV and outdoor units should be connected one unit after
another in a daisy chain from the outdoor unit to the final HRV unit. And the shielded layer must be
properly grounded, and a build-out resistor must be added to the last HRV unit to enhance the stability
of the communication system.
Incorrect wiring such as a star connection or a closed ring will cause instability of the communication
system and system control anomalies.
Use a three core shielded wire (greater than or equal to 0.75 mm2) for the communication wiring
between the indoor and outdoor units. Make sure the wiring is connected correctly. The connecting lead
for this communication wire must come from the master outdoor unit.
All shielded wiring in the network are interconnected, and will eventually connect to earth at the same
point " .
Sound power
level(dB)
Communication wiring between the indoor unit and wired controller
The wired controller and the indoor unit can be connected in different manners, depending on the forms of
communication.
1. For a bidirectional communication mode:
Use 1 wired controller to control 1 indoor unit or 2 wired controllers (one master and one slave
controller) to control 1 indoor unit.(see Fig.4-4)
Use 1 wired controller to control multiple indoor units or 2 wired controllers (one master and one slave
controller) to control multiple indoor units. The maximum number of connections is 16.(see Fig.4-5)
2. For single direction communication mode:
Use 1 wired controller to control 1 indoor unit
The X1/X2, D1/D2 ports on the sides of the main control board and single direction communication port
are for different types of wired controllers.
For the specific connection method, refer to the instructions in the corresponding wired controller
manual to carry out the wiring and connections.
Handling the Electrical Wiring Connection Points
Once the wiring and connections are done, use tie straps to secure the wiring properly so that the
connection joint cannot be pulled apart by external force. The connection wiring must be straight out so
that the cover of the electrical box is level and can be closed tightly.
Use professional insulation and sealing materials to seal and protect the perforated wires. Poor sealing
may lead to condensation, and entry of small animals and insects that may cause short circuits in parts
of the electrical system, causing the system to fail.
10
HRV-2B-Mi -D200
HRV-2B-Mi -D300
HRV-2B-Mi -D400
HRV-2B-Mi -D500
HRV-2B-Mi -D800
HRV-2B-Mi -D1000
HRV-2B-Mi -D1500
HRV-2B-Mi -D2000
HRV-2B-Mi -D200
HRV-2B-Mi -D300
HRV-2B-Mi -D400
HRV-2B-Mi -D500
HRV-2B-Mi -D800
HRV-2B-Mi -D1000
HRV-2B-Mi -D1500
HRV-2B-Mi -D2000