147
MODBUS registers
Address
register
Meaning Description
138 Water flow
Value read = current value* 100 [unit: m³/hour]
139
ODU frequency
limitation
Diagram value ----- ODU feedback 174
140 IDU capacity Value read = current value* 100 unit: kW
141 Solar T
142
Number of units in
cascade
BIT1-BIT15 represents the online/oine state of 1-1 5 units
BIT0 Reserved
143 High bit of electrical
Energy consumption
144 Low bit of electrical
145 High bit of heat
Heating capacity of the system
146 Low bit of heat
147
AHS power supply
output to EDGE series
Value read = current value* 10 (unit: V)