99
Start-up - initial settings and functions
Defines the maximum water supply temperature of the function.
START TIME (standard: current time - settable: 00:00/23:30)
Defines the start time of the function.
START DATE (standard: today - settable: 1-1-2000/31-12-2099)
Defines the start date of the function.
The HMI display shows the water supply temperature and the operating time of the function.
L
NOTE
You can forcibly exit the function by pressing .
12.3 EMPTY AHS CIRCUIT
Reserved parameter, do not change.
8.2.13 Automatic restart settings
MENU > FOR SERVICEMAN > 13. AUTO RESTART
The unit stores the user settings even after the power supply has been cut o.
This function sets whether the unit should automatically restart or remain on stand-by when the power sup-
ply is restored after a power failure.
The parameters that can be set for this function are:
13.1 COOL/HEAT MODE (standard: YES - settable: YES/NO)
Defines whether the automatic restart function is switched on for Cooling and Heating modes.
13.2 DHW MODE (standard: YES - settable: YES/NO)
Defines whether the automatic restart function is switched on for DHW mode.
8.2.14 Unit’s power supply limitation settings
MENU > FOR SERVICEMAN > 14. POWER INPUT LIMITATION
This function is used to limit the current consumed by the unit according to predefined profiles.
Maximum current limitation [A] according to the selected profile:
Size
#
2.1-3.1 4.1-5.1 6.1M-7.1M 8.1M 6.1T-8.1T 9.1 10.1 12.1 14.1
1 18 19 30 30 14 18 21 24 28
2 16 18 28 29 13 17 20 23 27
3 15 16 26 27 12 16 19 22 26
4 14 14 24 25 11 15 18 21 25
5 13 12 22 23 10 14 17 20 24
6 12 12 20 21 9 13 16 19 23
7 12 12 18 19 9 12.5 15 18 22
8 12 12 16 17 9 12 14 17 21
The settable parameter for this function is:
14.1 POWER LIMITATION (standard: NO - settable: NO/1 to 8)
Enables the function and defines the maximum consumption profile.
L
NOTE
By enabling the function, unit performance will be less than nominal.