COLASIT AG
Plastic construction
CH-3700 Spiez
Phone +41 (0)33 655 61 61 Fax +41 (0)33 654 81 61
TD-000 675-E
Edition 10/2019, Subject to alteration
Copyright by COLASIT AG Spiez
Page 14
Fault
Possible causes
Remedy
Restrictors not or only partly
open
Check opening on site
Intake or pressure duct blocked
Remove blockage
Fan fails to reach its rated
speed
Electrical switching
mechanisms incorrectly
adjusted
Check motor protection setting
and reset if necessary
Motor winding defective
Please consult the
manufacturer
Drive motor drive not correctly
designed
Please consult manufacturer
to verify starting torque
Grinding noises when fan is
running or starting
Intake duct fitted under tension
Remove intake duct an realign
13 Retrofittable original accessories
If not already a part of our scope of supply, these original parts are available ex stock when ordered.
- Frequency converters
- Roof-mounting plinth
- Insulated roof-mounting plinth
- Roof-mounting flange
- Fixing for wall-mounting
- Fixing for ceiling / floor-mounting
- Self-acting flap in intake
- Elastic sleeves
- Condensate drains
- Protective grating for intake-and outtake flap
14 Fan identification
The following rating plate is affixed to each COLASIT fan:
1 Manufacturer
2 Field for CE marking and applicable standards
3 ATEX-identification, for details see the section on Explosion Protection
4 Fan specifications: fan type, casing design, material of casing and impeller, order number and date of
manufacture.
5 Technical specifications
Part 2: Units
15 Design and function of the CRDV 200-315
All impellers in this series are balanced to better than Q 6.3 according to ISO 21940.
The casing with its thermoplastic rear panel is screwed onto the support base and can be easily dismantled
for inspection or cleaning purposes.
The fans are available in 2 standard designs
As a roof ventilator mounted on a roof-mounting plinth or on a chimney-pipe supplied by the customer
As an in-line fan mounted directly in ducting
As a basic principle, plastic fans are to be installed on the intake side in order to avoid leaks.