AnlInIOM3 lev2 [ ]
The level for IOM ANALOG INPUT 3 alarm detection.
Step: 1
Range: -100 - +10000
AnlInIOM3 del [s]
Delay for IOM ANALOG INPUT 3 alarm.
Step: 1 s
Range: 0 - 180 s
AnlInIOM4 lev1 [ ]
The level for IOM ANALOG INPUT 4 alarm detection.
Step: 1
Range: -100 - +10000
AnlInIOM4 lev2 [ ]
The level for IOM ANALOG INPUT 4 alarm detection.
Step: 1
Range: -100 - +10000
AnlInIOM4 del [s]
Delay for IOM ANALOG INPUT 4 alarm.
Step: 1 s
Range: 0 - 180 s
The protection of IOM/PTM inputs is activated by overcrossing the limits.
CalibrAInIOM 1,2,3,4 […]
Calibrating constant to adjust the measured value of IOM/PTM analog inputs. Physical dimension of
calibrating constant is corresponding to Analog input.
Step: 1
Range: -1000 – +1000
InteliLite – MRS10/11/15/16, SW version 2.2, ©ComAp – November 2004 37