AF10‐EControlConnector
5
TechSupport:1‐818‐841‐5500
BlastControl:Pin1provides115VACpowerfromtheAccuFlo.Thehostmustprovideaswitchtoputthis
voltagebackintoPin2,whichwillcausetheblastertoblast.WhenPin2isleftfloating,theblasterwillnot
blast.200mAofcurrentistypical.
PE: Pin4providesanoptionalbondingpathtoPrimaryEarththroughtheAccuFlo.Ifthehostisotherwise
bondedtoPE,donotusethispin.
RegulatorControl:Theregulatormustbepoweredby24vdcthroughPin7andgroundthroughPin6.The
regulatorrequires60mAofcurrent.Theblastpressureissetbyprovidinga0‐10vdcsignalatPin8,which
correspondstoapressureof0‐148psi.Theinternalresistanceoftheregulatorsinputis100ohmsminimum.
AF10‐ECablesandControllers
CablingandcontroldependsonhowtheuserdesirestocontroltheAF10‐E.Usetheabovetableto
determinewhichcabletouse.IftheAF10‐EispairedwithanAutoFillunit,refertotheAutoFillmanualfor
additionalwiringinformation.