CTK04 ComfortNet™ Communicating Thermostat
15
I/O-CHTSTAT03 69-2688—07
Heat pump with outdoor temperature lockouts
Outdoortemperaturelockoutsareoptional.SeeInstallerSetup
options(ISU3120).
Heat pump only
Heatpumpwithbackupheatasneeded*
Backupheatonly
Heat pump only
Heatpumporbackupheatoperates*
Backupheatonly
Outdoor temperatureOutdoor temperature
Backup heat lockout
Backup heat lockout
Compressor lockout
Compressor lockout
* No backup heat unless indoor temperature drops to selected Backup Heat Differential setting, or Backup Heat
Upstage Timer expires. Heat pump stays ON when backup heat turns on.
* No backup heat unless indoor temperature drops to selected Backup Heat Differential setting, or Backup
Heat Upstage Timer expires. Heat pump turns OFF when backup heat turns on.
Electric - Backup heat allowed to run with heat pump
Fossil Fuel - Backup heat NOT allowed to run with heat pump