12
systems with high thermal inertia (e.g. underoor heating), and the
±0.2 °C switching sensitivity (factory default setting) for heating
systems with low thermal inertia (e.g. at panel radiators). You can
read more about switching sensitivity in Chapter 5.
4.3 Switching between the Heating and Cooling Mode
The heating or the cooling mode of the thermostat can be selected
by the right jumper. With factory default settings the jumper is
located on the central and the uppermost pins, which selects the
heating mode. By relocating the jumper onto the bottommost and
central pins, the cooling mode can be selected. The output terminals
1 (NO) and 2 (COM) of the thermostat are closed below the set
temperature in heating mode, and they are closed above the
set temperature in cooling mode (taking the switching sensitivity
into account).