18 Notes on data register tables
7 Notes on data register tables
7.1 Software version 1.1.x.x
UInt16 register only
No decimals
e.g.:
>0,1 bar ... <1,0 bar = 0
>1,0 bar ... <2,0 bar = 1
>2,0 bar ... <3,0 bar = 2
etc.
Only imperial display via Modbus
Pressure values in bar
7.2 Software version 4.x.x.x
UInt16 register only
No decimals
Values rounded
e.g.:
>0,1 bar ... <1,5 bar = 1
>1,5 bar ... <2,5 bar = 2
>2,5 bar ... <3,5 bar = 3
etc.
Metric or imperial units according to the control unit settings of the corresponding device
7.3 Software version 5.x.x.x
Use of UInt16 and 32-Bit Float register
Decimals are shown by all 32-Bit Float registers
New register addresses for 32-Bit Float
7.4 Software version 5.3.x.x
When warning W35 "BMS Timeout" occurs, the device is stopped. The BMS timeout is only evaluated,
if the signal source under "Menu > Control Settings > Source" is not set to "Analog" (see chapter 6)
EL new register for "Operating status A unit" and "Operating status B unit"
EL new register for internal controller settings