EasyManua.ls Logo

Condair LINKS Series - Data Register el

Condair LINKS Series
40 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
30 Data register tables
8.5 Data register EL
Description Range Input Register 1-based Format
Read with Function 04
Operating status
unit A
0 = Humidifying
1 = Idle
2 = Idle Drain
3 = Keep Warm
4 = Filling
5 = Draining
6 = Disabled
7 = Safety Loop
10 = Blower Pack
11 = Stopped
12 = Partial Drain
13 = Self Test
31003
5)
UInt16
Maintenance and malfunction status
unit A
0 = Service Info
1 = Warning
2 = Service
3 = Fault
31004
Enable contact
unit A
0 = Open
1 = Closed
30002
Input signal channel 1
unit A
0 - 100 % 30004
Limiter signal channel 2
unit A
0 - 100 % 30005
System demand 0 - 100 % 30006
External safety loop
unit A
0 = Open
1 = Closed (ok)
30007
Blower ready
unit A
0 = Off
1 = On (ready)
30008
External fan
unit A
0 = Off
1 = On
30009
Enable contact
unit B
0 = Open
1 = Closed
30012
External safety loop
unit B
0 = Open
1 = Closed (ok)
30017
Blower ready
unit B
0 = Off
1 = On (ready)
30018
External fan
unit B
0 = Off
1 = On
30019
Contactor
unit A
0 = Off
1 = On
31200
Contactor
unit B
0 = Off
1 = On
31201
Inlet valve
unit A
0 = Closed
1 = Open
31202
Inlet valve
unit B
0 = Closed
1 = Open
31203
Drain pump
unit A
0 = Off
1 = On
31204
Drain pump
unit B
0 = Off
1 = On
31205

Related product manuals