25Data register tables
8.3 Data register RS
Description Range Input Register 1-based Format
Read with function 04
Input signal channel 1
unit A
0 - 100 % 30004
UInt16
Limiter signal channel 2
unit A
0 - 100 % 30005
System demand 0 - 100 % 30006
Device type
0 = RS
1 = RS+ RO
2 = RO
31000
Nominal voltage
0 = 200 V
1 = 208 V
2 = 230 V
3 = 240 V
4 = 400 V
5 = 415 V
6 = 440 V
7 = 460V
8 = 480 V
9 = 500 V
10 = 550 V
11 = 600 V
12 = 380 V
31003
Max. capacity
1)
5 - 160 kg/h
10 - 360 lb/hr
31016
32-Bit Float
7)
Max. capacity
unit A
1)
5 - 40 kg/h
10 - 90 lb/hr
31018
Max. capacity
unit B
1)
5 - 40 kg/h
10 - 90 lb/hr
31020
Actual capacity
1)
0 - 160 kg/h
0 - 360 lb/hr
31022
Actual capacity
unit A
1)
0 - 40 kg/h
0 - 90 lb/hr
31024
Actual capacity
unit B
1)
0 - 40 kg/h
0 - 90 lb/hr
31026
1)
According to the settings <Imperial> or <Metric> in the RS control unit
7)
32-Bit Float are only supported in software version 5.x.x.x or higher