22 Data register tables
8.2 Data register ME
Description Range Input Register 1-based Format
Read with function 04
Actual humidity or
demand
0 - 100 % 31300
32-Bit Float
7)
Actual air temperature
1)
°C or °F 31302
UV current 0 – 4.0 A 31304
Water capacity
1)
stage 1
5.0 - 200.0 kg/h
11.0 - 440.9 lb/h
31306
Water capacity
1)
stage 2
5.0 - 200.0 kg/h
11.0 - 440.9 lb/h
31308
Water capacity
1)
stage 3
5.0 - 200.0 kg/h
11.0 - 440.9 lb/h
31310
Water capacity
1)
stage 4
5.0 - 200.0 kg/h
11.0 - 440.9 lb/h
31312
Water capacity
1)
stage 5
5.0 - 200.0 kg/h
11.0 - 440.9 lb/h
31314
Water capacity
1)
stage 6
5.0 - 200.0 kg/h
11.0 - 440.9 lb/h
31316
Water capacity
1)
stage 7
5.0 - 200.0 kg/h
11.0 - 440.9 lb/h
31318
Operating hours 0 - 1'200'000 h 31320
Next service 0 - 10000 h 31322
Next UV bulb exchange 0 - 450 d
6)
31324
Next PureFlow Ag+ exchange 0 - 365 d
6)
31326
Conductivity μS 31328
Actual water
temperature
1)
°C or °F 31330
Incoming air
temperature
1)
°C or °F 31332
Demand pump 1 0 - 100 % 31341
UInt16
Demand pump 2 0 - 100 % 31342
Demand pump 3 0 - 100 % 31343
Demand pump 4 0 - 100 % 31344
Demand pump 5 0 - 100 % 31345
Demand pump 6 0 - 100 % 31346
Demand pump 7 0 - 100 % 31347
Water lever in tub 0 - 8 31203
1)
According to the settings <Metric> or <Imperial> in the ME control unit. Metric units via Modbus are not supported in software
version 1.1.x.x
6)
Unit days as of software version 5.7.x.x
7)
32-Bit Float are only supported as of software version 5.x.x.x or higher