EasyManua.ls Logo

Condair LINKS Series - Page 23

Condair LINKS Series
40 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
23Data register tables
Description Range Input Register 1-based Format
Read with function 04
Number of running stages 0 – 7 31002
UInt16
Operating status
0 = Initializing
1 = Diagnostic
2 = Stopped
3 = Humidifying
4 = Cooling
5 = Holding
6 = Draining
7 = Refreshing
8 = Filling
9 = Standby
10 = Diluting
11 = Drain assisting
12 = Bleeding
13 = Ramping Up
14 = Switched Off
15 = Remote Off
16 = Purging
17 = Drain check
31010
Maintenance and
malfunctions status
0 = Service Info
1 = Warning
2 = Service
3 = Rell Liquid
4 = Replace PureFlow Ag+
5 = Replace UV Bulb
6 = Matrix Wash over
7 = Out of Comissioning
8 = Activation Code
9 = Fault
31013
Error code
2)
0 = No error 31014
Fault pump 1
4)
0 = Fault
1 = Ok
31031
Fault pump 2
4)
0 = Fault
1 = Ok
31032
Fault pump 3
4)
0 = Fault
1 = Ok
31033
Fault pump 4
4)
0 = Fault
1 = Ok
31034
Fault pump 5
4)
0 = Fault
1 = Ok
31035
Fault pump 6
4)
0 = Fault
1 = Ok
31036
Fault pump 7
4)
0 = Fault
1 = Ok
31037
Fault inlet
4)
0 = Fault
1 = Ok
31040
Fault water temperatur
4)
0 = Fault
1 = Ok
31041
Fault water outlet
4)
0 = Fault
1 = Ok
31042
Fault level sensor
4)
0 = Fault
1 = Ok
31043
Fault water conductivity
4)
0 = Fault
1 = Ok
31044
Safety loop
0 = Open
1 = Closed (=ok)
31200

Related product manuals