21Data register tables
Description Range Input Register 1-based Format
Safety loop
0 = Open
1 = Closed (=ok)
31200
UInt16
Y1 inlet valve
0 = Closed
1 = Open
31201
Y2 valve
0
1
31202
Y3 valve
air cleaning
0 = Closed
1 = Open
31203
Y4 valve
external pipe ush
0 = Closed
1 = Open
31204
Y5 valve
spray circuit
0 = Closed
1 = Open
31205
Y6 valve
spray circuit
0 = Closed
1 = Open
31206
Y7 valve
spray circuit
0 = Closed
1 = Open
31207
Y8 valve
spray circuit
0 = Closed
1 = Open
31208
Y9 valve
spray circuit
0 = Closed
1 = Open
31209
Y10 valve
drain (NO)
0 = Open
1 = Closed
31210
Y11 auxiliary outlet valve
0 = Open
1 = Closed
31211
FC enable
0 = Disable
1 = Enable
31212
1)
According to the settings <Metric> or <Imperial> in the DL control unit. Metric units via Modbus are not supported in software
version 1.1.x.x
2)
Error Code is not supported in software version 1.1.x.x. See Error code description in the malfunction list of the operation
manual.
3)
psi is not implemented in software version 4.209.x.x and 1.1.x.x
7)
32-Bit Float are only supported in software version 5.x.x.x or higher
Description Range Holding Register 1-based Format
Read with function 03
Write with function 06
Humidity setpoint 0 - 95 % 41005
UInt16
Proportional band 6 - 65 % 41006
Integral time 1 - 60 min 41007
Manual capacity 20 - 100 % 41008
Actual humidity or
demand via Modbus
0 - 100 % 41053
Remote ush
0 = Stop ush
1 = Start ush
41707